Information based on query as of Thursday, July 18, 2024.
Permit Information
Permit NumberFIR02-00316
StatusFinaled
Name ALARMCO
Site Address 9950 W USTICK RD
Project Namealm-NEW HEIGHTS CHRISTIAN
Customer Number 
ePlanReview 
Description
NEW HEIGHTS CHRISTIAN FELLOWSHIP - To extend the existing fire alarm system into the new addition and to modify the existing devices within the existing building area to meet current code. The system includes manual pull stations, monitoring of the fire sprinkler system, partial area smoke detection including for release of smoke door hold-opens, monitoring of smoke detectors for HVAC air handler shut down and fire/smoke damper release, and a/v annunciation with speaker/strobes for voice evacuation.
The associated building permit (BLD 02-00155) is to construct a 17,367 square foot one story, Type V1hr sanctuary with classrooms, office, kitchen, and narthex addition to the existing building. A 2 hr area wall will separate the existing building from the addition and one-hour occupancy separations will be provided for between the Group B and A2.1 Occupancies. All work is per the approved plans and attachments. The new addition shall be fully fire sprinklered and the sprinklers shall be used for substitution of the one hour construction except for the rated corridor on the east side and the area and occupancy separations.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/14/20035/14/20035/14/2003PPASS
DetailsTroy Cobbley
fire alarms finaled 5/14/2003 10:50:46 AM
INSP-Final Inspection5/12/20035/13/20035/13/2003APART
DetailsTroy Cobbley
The audio in the santuary does not meet the 75 db requirement. A temporary occupancy was given until the problem can be remedied. The temporary occupancy was given with Dave Millers permission 5/13/2003 10:27:45 AM
INSP-Final Inspection5/12/20035/12/20035/12/2003PPASS
DetailsTroy Cobbley
Retest the hood for light and recepticle shutdown. Provide panel keys for knox box. Provide map for facp. Provide room numbers on map. Lounge 130 pull station is mis labeled. Verify signals with fax 5/12/2003 3:23:41 PM
INSP-Final Inspection5/8/20035/9/20035/9/2003AFAIL
DetailsTroy Cobbley
Strobes exceed 15' from the ends of corridors and manual pull stations exceed 5' from door in several locations. Fire alarm system had a trouble generated from somewhere on the sprinkler system. No inspection done. See approved job site plans for specific locations. All fire sprinkler monitoring devices and alarm devices need tested 5/9/2003 11:42:22 AM
INSP-Conference2/12/20032/12/20032/12/2003ADONE
DetailsTroy Cobbley
I called Alarmco and spoke to Teresa about getting the alarm resubmittals in for review since it had been six months since their last submittals. Alarmco was on the job today.