Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR02-00325
StatusFinaled
Name J R SIMPLOT (BIOLAB)
Site Address 5369 W IRVING ST
Project NameJ R SIMPLOT BIOLAB
Customer Number 
ePlanReview 
Description
To provide two duct smoke detectors in the supply and return ducts for release of fire/smoke dampers. The associated building permit (BLD 02-01077) is to remodel of existing office space in a 18,000 sq.ft. building to expand the existing 1437 sq ft Biolab by remodeling the 680 sq ft office to create one 2117 sq ft "Lab Block" per approved plans on file. Work will include, construction of a one hour occupancy separation wall, installation of two new Exhaust hoods, installation of new counters, relocation of a one-hour fire assembly door, Miscellaneous related interior finishes. NOTE: This building is fully fire sprinklered to allow for increases in hazardous materials. All alterations or modifications to the existing fire sprinkler system shall be per NFPA #13 as regulated by the fire department.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/23/20034/24/20034/24/2003APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/23/2003 at 2:18:51 PM. Contact: ###-####. tested in-duct detector; damper closed 4/24/2003 10:21:10 AM
INSP-Final Inspection3/17/20033/18/20033/18/2003PFAIL
DetailsTroy Cobbley
In-duct detector did not work 3/18/2003 1:06:18 PM
INSP-Final Inspection1/30/20031/31/20031/31/2003PNR
DetailsTroy Cobbley
ADT was not ready for the inspection 1/31/2003 2:04:13 PM
INSP-Final Inspection1/21/20031/24/20031/24/2003PFAIL
DetailsTroy Cobbley
###-#### matt The south in-duct smoke detector did not operate and needs to be tested. Provide map at the FACP. Verify dedicated circuit location 1/24/2003 3:59:07 PM
INSP-Final Inspection10/11/200210/14/200210/14/2002PCANC
DetailsTroy Cobbley
duplicate inspection. The contractor said he punched in the wrong button and forgot to cancell 10/14/2002 4:27:08 PM
INSP-Final Inspection10/11/200210/14/200210/14/2002AFAIL
DetailsTroy Cobbley
verify dedicated electrical circuit to FACP has been completed, clean up wiring in the FACP, verify batteries in FACP are supervised after the panel gets cleaned up, duct smoke detectors do nto activate the fie smoke dampers as per the review comments, change labeling on the new tamper switch 10/14/2002 10:48:58 AM
INSP-Final Inspection10/8/200210/10/200210/10/2002PCANC
DetailsTroy Cobbley
contractor cancelled 10/10/2002 3:15:32 PM