INSP-Final Inspection | 12/12/2002 | 12/12/2002 | 12/12/2002 | A | PASS |
Troy Cobbley
|
|
|
fire alarm system finaled
|
INSP-Alarm Testing | 12/11/2002 | 12/13/2002 | 12/11/2002 | P | CANC |
Troy Cobbley
|
|
|
Troy, If you could call me and let me know as far in advance when you will be able to make it out to Emser Tile on Friday I would appreciate it. My cell number is ###-####, and the office is ###-####.
Thanks,
Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick
|
INSP-Sprinkler Rough-in/Hydro | 12/11/2002 | 12/11/2002 | 12/11/2002 | P | CANC |
Troy Cobbley
|
|
|
the fire alarm contractor could not make it to the inspection 12/11/2002 3:42:44 PM
|
INSP-Final Inspection | 12/3/2002 | 12/3/2002 | 12/3/2002 | A | FAIL |
Troy Cobbley
|
|
|
relocate the smoke detector above the FACP to the deck, provide the correct battery size, provide the correct Boise Fire Dept. approved knox key box, provide lock on breaker and paint, neither phone line give a trouble when disconnected. I stopped the inspection. No other items looked at or tested
|
INSP-Alarm Testing | 11/26/2002 | 12/2/2002 | 12/2/2002 | P | CANC |
Troy Cobbley
|
|
|
cancelled by the contractor until tomorrow 12/2/2002 4:25:30 PM
|