Permit Information
Permit NumberFIR02-00372
StatusFinaled
Name PROTEX
Site Address 415 N MAPLE GROVE RD
Project Namealm-Preco
Customer Number 
ePlanReview 
Description
Preco - To replace an existing fire alarm system. The proposed system is a manual fire alarm system, and includes fire sprinkler monitoring and monitoring of duct detectors for HVAC for air handler shutdown.
No associated building permit is indicated.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/18/20039/18/20039/18/2003PPASS
DetailsTroy Cobbley
This is Patricks Cell Phone.
Have a Great Day Today.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
INSP-Final Inspection4/23/20034/25/20034/25/2003AFAIL
DetailsTroy Cobbley
Provide map for fire alarm system, remove old fire alarm equipment, reverify alarm signals 4/25/2003 9:57:45 AM
INSP-Final Inspection4/7/20034/8/20034/8/2003ACANC
DetailsRick Jackson
PATRICK; Phone #: ###-#### Internet Inspection Request from: Darla Downs per Troy 4/8/2003 7:44:54 AM
INSP-Final Inspection4/7/20034/7/20034/7/2003PCANC
DetailsTroy Cobbley
Troy, This is Patricks cell.
Thanks Have a good day.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley TROY CALLED TO HAVE ME CANC THIS INSPECTION AND TO PUT IT IN FOR 4-8-03 AM
INSP-Final Inspection4/4/20034/4/20034/4/2003PFAIL
DetailsTroy Cobbley
Horn/strobes have been added in deficiant areas and the sound level is now ok. No other items tested 4/4/2003 4:00:19 PM
INSP-Final Inspection3/28/20033/31/20033/31/2003PFAIL
DetailsTroy Cobbley
This is Patrick Cell; Phone #: ###-#### This inspection turned into a conference. The a/v's work but devices need to be added on a mezzanine area and in multiple offices. Also the audio does not meet the minimum 75 db requirements in all areas. The fire sprinkler devices have been tested but the signals did not come in right. All pull stations worked. No other devices tested. 3/31/2003 3:19:21 PM
INSP-Final Inspection11/19/200211/20/200211/20/2002AFAIL
DetailsTroy Cobbley
provide mechanical plans, provide additional duct smoke detectors as required and resubmit plans for review, duct detectors did not shut down the hvac units as required, remove all non functioning fire alarm devices (old system), and relocate the manual pull stations as per the review comments.. NO OTHER ITEMS VERIFIED OR TESTED 11/20/2002 11:11:31 AM