INSP-Final Inspection | 11/21/2003 | 11/21/2003 | 11/21/2003 | P | PASS |
Troy Cobbley
|
|
|
finaled 7-3-2003
|
INSP-Final Inspection | 7/2/2003 | 7/3/2003 | 7/3/2003 | P | FAIL |
Troy Cobbley
|
|
|
Project not ready for a final inspection yet. Underground supply flush was OK though 7/3/2003 4:06:59 PM
|
INSP-Final Inspection | 6/30/2003 | 6/30/2003 | 6/30/2003 | P | FAIL |
Troy Cobbley
|
|
|
Install wiring connections in devices or boxes per NFPA 70 for all fire alarm devices 6/30/2003 3:04:39 PM
|
INSP-Final Inspection | 6/4/2003 | 6/5/2003 | 6/5/2003 | A | FAIL |
Troy Cobbley
|
|
|
Provide knox box, provide sign on fire alarm/riser door, clean up all duct detector wiring, rotate sample tube in duct detector in daycare(zone 128), provide filter for duct detector in Joey's Seafood, repair wiring and test hood in the Mongolian BBQ. 6/5/2003 11:07:33 AM
|
INSP-Final Inspection | 6/3/2003 | 6/4/2003 | 6/4/2003 | A | PART |
Troy Cobbley
|
|
|
Started the inspection. Was not able to finish. To be continued tomorrow. 6/4/2003 11:17:04 AM
|
INSP-Final Inspection | 5/29/2003 | 5/30/2003 | 5/29/2003 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 5/29/2003 at 9:38:27 AM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 29 2003 3:21PM.
|
INSP-Final Inspection | 5/23/2003 | 5/28/2003 | 5/27/2003 | P | CANC |
Troy Cobbley
|
|
|
Scheduled by a contractor via Hello! on 5/23/2003 at 2:41:24 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on May 27 2003 4:20PM.
|
INSP-Alarm Testing | 5/15/2003 | 5/16/2003 | 5/16/2003 | A | PART |
Troy Cobbley
|
|
|
The duct smoke detector over Basilio's restraunt that was previously not working now functions correctly 5/16/2003 10:30:17 AM
|
INSP-Alarm Testing | 5/9/2003 | 5/9/2003 | 5/9/2003 | P | FAIL |
Troy Cobbley
|
|
|
North hvac unit in the Basilio's restraunt would not operate. It is locked out until it can be repaired and tested. Smoke detector over panel, battery troubles, phone lines and pull station have been tested. No other items tested. This initial test was just to get the restraunt a temp occupancy. The main inspection to be called in next week. 5/9/2003 2:47:53 PM
|
INSP-Alarm Testing | 11/27/2002 | 11/27/2002 | 11/27/2002 | A | NR |
Troy Cobbley
|
|
|
A temporary occupancy was given with Dave Millers permission for the California Marketplace TI until the fire alarm system has been permited and inspected. The owner has until 2-28-03 to complete work. See letter dated 11-21-02.
|