Permit Information
Permit NumberFIR03-00006
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 1055 N CURTIS RD
Project NameSPR SARMC-PARKING GARAGE
Customer Number 
ePlanReview 
Description
Saint Alphonsus Regional Medical Center (East Parking Garage) - To install a Class 1, Manual, Dry Standpipe system in a new 83,600 ft/2, two-level, concrete parking garage on the east side of the Saint Alphonsus Regional Medical Center Campus. The top deck being at street level and one deck below. This garage is an open parking garage with exterior openings at the North and East sides of the structure. This building is structurally designed to support one additional future parking level. This garage is not fire sprinklered. The piped system shall comply with NFPA 14-2000, NFPA 13-1999 (where addressed), attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-02583.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/200310/31/200310/31/2003APASS
DetailsTroy Cobbley
INSP-Sprinkler Rough-in/Hydro9/2/20039/2/20039/2/2003PPART
DetailsTroy Cobbley
provide as-builts to the city of boise showing the new hose vavle locations, provide EQ bracing on the 4" piping in the locations as discussed, provide signage for the stand pipe per review notes, provide verification that there is adequate clearance for hose hookup at the top north hose vavle with the fire dept. Hydro test is OK 9/2/2003 3:04:21 PM 9/2/2003 3:08:33 PM
INSP-Conference8/7/20038/11/20038/11/2003ADONE
DetailsTroy Cobbley
The sprinkler contractor is requesting the relocation of the hose valves at the south end of the project. It appears the hose vavles will still meet NFPA 14 spacing requirements but they will need to contact Bill Alexander for final approval and resubmit an as-built before final approval 8/11/2003 11:01:45 AM
INSP-Conference6/26/20036/26/20036/26/2003PDONE
DetailsTroy Cobbley
mike; Phone #: ###-#### Hose valves relocated and elevation changed. This is for the two vavles located in the egress path. OK per Bill Alexander and I. 6/26/2003 4:17:22 PM