Permit Information
Permit NumberFIR03-00012
StatusFinaled
Name MOUNTAIN ALARM
Site Address 5380 W FRANKLIN RD
Project Namealm-AMERICAN RED CROSS
Customer Number 
ePlanReview 
Description
To replace an existing fire alarm panel to provide code compliant fire sprinkler monitoring for this building. Since all system components are affected by a FAC panel replacement, a full alarm system upgrade to meet current codes is required at the time of any FAC panel replacement. Therefore the scope of this project will include a review of the entire alarm system. The existing building alarm system also includes voluntary manual pull stations at all exits at every level and audible alarm annunciation throughout the building. No visual alarms are provided.

The associated building permit (BLD 02-00410) is to perform selective demolition per plans and to remodel a 1,600 sq. ft portion of the basement to create Lab, Labeling, Mechanical & Communications rooms; remodel 820 sq. ft. on the 1st floor for a Lab area and installation of a walk-in cooler per approved plans on file. Work to include construction of interior non-bearing walls & finishes; mechanical, electrical, plumbing & fire sprinkler upgrades; suspended ceiling installation; walk-in cooler & cabinetry; and maintenance of floor/ceiling draft stop systems. NOTE: This building is fully sprinklered. A "Letter of Completion / Compliance" is required for final occupancy & use approval as a condition of this permit. PC#02-120/drs

6/18/2004 - On 5/18/2004, phone call to Lynde Jones at Mt Alarm to explain the plan modification was required to show all the security devices and the doors they are controlling beside the releasing mechanism of the fire alarm system. She stated they would get that information on the plans and resubmit. I received revised plans on 6/17/2004, started a plan review today and found that no security devices have been placed on the drawings. A resubmittal is required. I phoned Lynde to advise of the situation. She will call on Monday to set up a meeting to resolve this issue.

7/9/2004 - Received revised plans indicating the locations of the doors and the security devices associated with them. There are six (6) doors shown on the basement plan and six (6) doors shown on the first floor plan. The PDS Fire Inspector shall field verify the functionality of these doors per IFC 1003.3.1.3.4.

7/30/2004 - Received complete resubmittal. Revised plans, riser, calcs and cutsheets. Item #8 has revised battery calculations.

10/22/2004 - Revised scope of work: To replace an existing fire alarm system with an addressable FACP. The required sprinkler monitoring fire alarm system includes manual pull stations, HVAC shutdown, elevator recall/shutdown and voluntary audible/visual notification throughout.

12/14/2004 - Received a revised building layout and fire alarm system modifications. The RTS for the HVAC shutdown are now located in the ceiling tiles below the unit, the elevator machine room has been relocated on the plans to match the building. Comment #5 regarding the horn/strobe in the stairwell still applies, it is shown on the plans and should NOT be installed.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/3/20052/4/20052/4/2005APASS
DetailsTroy Cobbley
Fire alarm finally finaled! 2/4/2005 11:02:58 AM
INSP-Final Inspection1/26/20051/27/20051/27/2005AFAIL
DetailsTroy Cobbley
Inspection was to verify that the waterflow switch is still intermittent as far as timing. It appears that the water for the sprinkler system is surging which won't allow the flow switch to activate. I left correction notice with Mountain Alarm and Eric with Red Cross 1/27/2005 8:17:47 AM
INSP-Final Inspection1/26/20051/27/20051/27/2005ANR
DetailsRick Jackson
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Talked to Linda and the flow switch problem has been turned over to Viking 1/27/2005 8:15:50 AM
INSP-Final Inspection1/7/20051/7/20051/7/2005PFAIL
DetailsTroy Cobbley
Bells still did not ring within 90 seconds 1/7/2005 2:29:29 PM
INSP-Final Inspection1/5/20051/6/20051/6/2005PFAIL
DetailsTroy Cobbley
Waterflow did not come into panel within 90 seconds 1/6/2005 1:11:38 PM
INSP-Final Inspection12/16/200412/17/200412/17/2004PFAIL
DetailsTroy Cobbley
Need two a/v's relocated to within 15' of the end of the corridor on the third floor and in the basement. Replace the door holder on the first floor and provide as builts. 12/17/2004 1:49:24 PM
INSP-Alarm Testing12/14/200412/15/200412/15/2004PFAIL
DetailsTroy Cobbley
See correction notice and approved plans for items needing attention 12/15/2004 4:13:09 PM
INSP-Alarm Testing12/7/200412/8/200412/8/2004AFAIL
DetailsTroy Cobbley
Inspection stopped after testing initiating devices on the first and second floors. Third floor not looked at. Elevator recall and sprinkler flow not done nor duct detectors on the roof. Monitoring company did not receive trouble for loss of phone lines, a/c power or loss of batteries. Resubmittals required. See city approved plans for specific locations and deficiencies. 12/8/2004 2:58:42 PM
INSP-Alarm Testing8/3/20048/4/20048/4/2004PFAIL
DetailsTroy Cobbley
Provide resubmittals showing the correct wiring for initiating zones and show door hold opens. Provide "Request to Exit" buttons per IFC 1003.3.1.3.4. See review notes. Provide correct count of horns. Provide verification of note #9. Need to retest pull stations and fire sprinkler items and horns on second floor. A re-inspection fee will apply upon the next inspection. 8/4/2004 4:25:07 PM
INSP-Final Inspection3/19/20043/19/20043/19/2004PFAIL
DetailsTroy Cobbley
Plans need to be resubmitted showing the new door magnet/security interface. Items tested today are both phone lines, vavle tamper switch and battery calculations which are ok. The smoke detector is now approved to be used with this panel. 3/19/2004 4:34:10 PM
INSP-Final Inspection6/4/20036/6/20036/6/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 6/4/2003 at 9:39:28 AM. Contact: ###-####. started to test sprinkler flow but couldn't locate inspectors test (after checking the exterior it appears to be on the northwest side of the building); need compatibility for smoke above panel; this is all that was done for today; they will reschedule for 6/9/03 to finish 6/6/2003 5:07:43 PM
INSP-Final Inspection3/18/20033/19/20033/19/2003PFAIL
DetailsTroy Cobbley
provide the correct smoke detector as per the submittals, verify a dedicated circuit, provide map, verify battery standby once the dedicated circuit is found, provide sign on door, test all initiating devices and verify signals 3/19/2003 4:14:10 PM
INSP-Final Inspection2/19/20032/21/20032/21/2003PCANC
DetailsTroy Cobbley
nicole ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--cancel per pam