INSP-Final Inspection | 2/3/2005 | 2/4/2005 | 2/4/2005 | A | PASS |
Troy Cobbley
|
|
|
Fire alarm finally finaled! 2/4/2005 11:02:58 AM
|
INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was to verify that the waterflow switch is still intermittent as far as timing. It appears that the water for the sprinkler system is surging which won't allow the flow switch to activate. I left correction notice with Mountain Alarm and Eric with Red Cross 1/27/2005 8:17:47 AM
|
INSP-Final Inspection | 1/26/2005 | 1/27/2005 | 1/27/2005 | A | NR |
Rick Jackson
|
|
|
linda; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Talked to Linda and the flow switch problem has been turned over to Viking 1/27/2005 8:15:50 AM
|
INSP-Final Inspection | 1/7/2005 | 1/7/2005 | 1/7/2005 | P | FAIL |
Troy Cobbley
|
|
|
Bells still did not ring within 90 seconds 1/7/2005 2:29:29 PM
|
INSP-Final Inspection | 1/5/2005 | 1/6/2005 | 1/6/2005 | P | FAIL |
Troy Cobbley
|
|
|
Waterflow did not come into panel within 90 seconds 1/6/2005 1:11:38 PM
|
INSP-Final Inspection | 12/16/2004 | 12/17/2004 | 12/17/2004 | P | FAIL |
Troy Cobbley
|
|
|
Need two a/v's relocated to within 15' of the end of the corridor on the third floor and in the basement. Replace the door holder on the first floor and provide as builts. 12/17/2004 1:49:24 PM
|
INSP-Alarm Testing | 12/14/2004 | 12/15/2004 | 12/15/2004 | P | FAIL |
Troy Cobbley
|
|
|
See correction notice and approved plans for items needing attention 12/15/2004 4:13:09 PM
|
INSP-Alarm Testing | 12/7/2004 | 12/8/2004 | 12/8/2004 | A | FAIL |
Troy Cobbley
|
|
|
Inspection stopped after testing initiating devices on the first and second floors. Third floor not looked at. Elevator recall and sprinkler flow not done nor duct detectors on the roof. Monitoring company did not receive trouble for loss of phone lines, a/c power or loss of batteries. Resubmittals required. See city approved plans for specific locations and deficiencies. 12/8/2004 2:58:42 PM
|
INSP-Alarm Testing | 8/3/2004 | 8/4/2004 | 8/4/2004 | P | FAIL |
Troy Cobbley
|
|
|
Provide resubmittals showing the correct wiring for initiating zones and show door hold opens. Provide "Request to Exit" buttons per IFC 1003.3.1.3.4. See review notes. Provide correct count of horns. Provide verification of note #9. Need to retest pull stations and fire sprinkler items and horns on second floor. A re-inspection fee will apply upon the next inspection. 8/4/2004 4:25:07 PM
|
INSP-Final Inspection | 3/19/2004 | 3/19/2004 | 3/19/2004 | P | FAIL |
Troy Cobbley
|
|
|
Plans need to be resubmitted showing the new door magnet/security interface. Items tested today are both phone lines, vavle tamper switch and battery calculations which are ok. The smoke detector is now approved to be used with this panel. 3/19/2004 4:34:10 PM
|
INSP-Final Inspection | 6/4/2003 | 6/6/2003 | 6/6/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 6/4/2003 at 9:39:28 AM. Contact: ###-####. started to test sprinkler flow but couldn't locate inspectors test (after checking the exterior it appears to be on the northwest side of the building); need compatibility for smoke above panel; this is all that was done for today; they will reschedule for 6/9/03 to finish 6/6/2003 5:07:43 PM
|
INSP-Final Inspection | 3/18/2003 | 3/19/2003 | 3/19/2003 | P | FAIL |
Troy Cobbley
|
|
|
provide the correct smoke detector as per the submittals, verify a dedicated circuit, provide map, verify battery standby once the dedicated circuit is found, provide sign on door, test all initiating devices and verify signals 3/19/2003 4:14:10 PM
|
INSP-Final Inspection | 2/19/2003 | 2/21/2003 | 2/21/2003 | P | CANC |
Troy Cobbley
|
|
|
nicole ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie--cancel per pam
|