INSP-Final Inspection | 11/4/2010 | 11/4/2010 | 11/4/2010 | A | PASS |
Forrest France
|
|
|
Permit finaled.
|
FIR-Aging Inspection | 11/3/2010 | 11/3/2010 | 11/3/2010 | | PASS |
Forrest France
|
|
|
|
FIR-Aging Inspection | 8/2/2010 | 8/2/2010 | 8/10/2010 | | PASS |
Forrest France
|
|
|
Okay for final
|
FIR-Aging Inspection | 5/21/2010 | 5/21/2010 | 5/21/2010 | | PASS |
Forrest France
|
|
|
|
INSP-Alarm Testing | 5/12/2003 | 5/14/2003 | 5/14/2003 | A | FAIL |
Rick Jackson
|
|
|
tested all AHU's for shutdown and smoke/fire damper shutdown - dampers closed on AHU shutdown; tested all overhead doors except for baggage system doors - all okay; still need to test dry sprinkler system and baggage system doors; will need to reverify the alarm system at final 5/14/2003 12:45:12 PM
|
INSP-Alarm Testing | 5/9/2003 | 5/12/2003 | 5/12/2003 | P | FAIL |
Rick Jackson
|
|
|
audible alarms in mechanical rooms; smoke/fire dampers aren't when AHU's are in fault; tested notification in all areas - okay; 5/12/2003 4:35:54 PM
|
INSP-Final Inspection | 5/8/2003 | 5/9/2003 | 5/9/2003 | A | FAIL |
Rick Jackson
|
|
|
###-#### robert Node 4 has ground fault; labels on several detectors not correct - see mapnet listing; strobes overspaced in mezzanine; nned to test dry sprinkler system and all troubles for TAC panels; need to test alarm condition for proper noise levels through speakers; need to drop test all overhead doors; ned to test troubles on main FACP; need programmed button labels on main FACP 5/9/2003 5:00:02 PM
|