Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR03-00035
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 7960 W NORTHVIEW ST
Project NameSPR UG ST MARK'S CATHOLIC CHU
Customer Number 
ePlanReview 
Description
(Building Area "B" New Church) * To install 6" C-900 underground into a new 26,050 ft/2 single story, sanctuary and to within 6" of the finish floor. This building will be fully fire sprinklered for one-hour substitution. The underground fire sprinkler system installation and related work shall comply (but may not be limited) to: NFPA 13-1999, NFPA 24-1995, attached review comment and conditions list, as regulated by the Boise City Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this permit work, to provide witness of compliance verification of minimum code. This permit is attached to BLD02-02454.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection1/21/20041/21/20041/21/2004APASS
DetailsTroy Cobbley
INSP-Sprinkler Rough-in/Hydro7/30/20037/30/20037/30/2003PPASS
DetailsTroy Cobbley
Underground hydro test is ok 7/30/2003 3:21:23 PM
INSP-Supply line flush3/17/20033/19/20033/19/2003APART
DetailsTroy Cobbley
The 6" underground supply was flushed. Out of a 4" outlet we got 3 1/4 psi which translates to 780 gallons. This flow needs to be verified to see if it will meet any of the exceptions to the 880 gallons required in NFPA 13 3/19/2003 11:22:24 AM
INSP-Supply line flush3/19/20033/19/20033/19/2003PPASS
DetailsTroy Cobbley
The valve at the street was half way closed. Flushed UG with open valve and everything looks good
INSP-Conference2/5/20032/6/20032/6/2003APASS
DetailsTroy Cobbley
inspection was for the underground fire sprinkler supply. Piping is OK for cover 2/6/2003 11:22:54 AM