Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberFIR03-00060
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 162 E WISHBONE CT
Project NameSPR ARTISTRY HOMES
Customer Number 
ePlanReview 
Description
Artisty Homes * Lot 7, Block 1, Sumac Subdivision * This structure requires an NFPA 13D automatic fire sprinkler protection system. To fire sprinkler a 1,852 ft/2 two story single-family dwelling (with a 494 ft/2 attached two car garage, a 54 ft/2 covered deck off master bedroom and partially covered walkway/patio areas). 1st floor 915 ft/2, 2nd floor 937 ft/2. The fire sprinkler water flow alarm shall be attached to the residence smoke detection system. All fire sprinkler work and related (which includes dual service water supply), backflow prevention (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review notes, as regulated by the Fire Department. This permit is attached to: BLD02-02781. This is one requirements indicated on Boise Fire Department Memorandum dated 09/04/2001 for the Final Plat.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/3/20039/3/20039/3/2003PPASS
DetailsRick Jackson
INSP-Final Inspection9/2/20039/2/20039/2/2003PFAIL
DetailsRick Jackson
flow switch not tied into any interior alarm notification device
INSP-Sprinkler Rough-in/Hydro3/17/20033/17/20033/17/2003PFAIL
DetailsRick Jackson
john; Phone #: ###-#### Internet Inspection Request from: Annette Moore need 1 inch meter as 3/4 inch is installed; need Ames BFP as Watts is installed; need domestic shut off before sprinkler controls; need to move heads one foot away from ceiling heat vents; 3/17/2003 3:27:31 PM