Permit Information
Permit NumberFIR03-00075
StatusFinaled
Name PROTEX
Site Address 420 W MAIN ST
Project Namealm - VELTEX BUILDING-SHELL
Customer Number 
ePlanReview 
Description
To provide a automatic/manual fire alarm system per code requirements. The fire alarm system will include sprinkler monitoring, elevator recall, HVAC monitoring and fire/smoke damper monitoring.
The associated building permit (BLD 02-02126) is to construct a new five-story, with a basement parking garage, 53,265 sq. ft. Type II 1-Hour, shell and core mixed-use building. NOTE: Stand pipes and the installation of a NFPA 13 fire sprinkler system is required for story increase and cannot be used for any other purpose.

Annunciation is not included for the future tenants on the ground, second or the third floors. No occupancy is permitted until a separate fire alarm permit has been issued. Occupancy of these areas is not permitted under this permit. A separate fire alarm permit will be required to install fire alarm devices before these areas may be occupied.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/19/20045/19/20045/19/2004PPASS
DetailsRick Jackson
INSP-Conference1/14/20041/14/20041/14/2004PPART
DetailsRick Jackson
Talked to Jim of Power Plus and he said all as-builts were provided to Rob (Protex) so all modifications could be incorporated into resubmittals 1/14/2004 3:05:42 PM
INSP-Final Inspection1/12/20041/12/20041/12/2004PFAIL
DetailsRick Jackson
doors with mag locks on south exit will need to release with fire alarm; awaiting calc's for batteries as meter reading indicated higher batteries will be needed; remove all covers from smoke detectors 1/12/2004 3:27:16 PM
INSP-Final Inspection1/8/20041/8/20041/8/2004AFAIL
DetailsRick Jackson
standby power draw is higher than calcs (340) so larger amp batteries are needed; resubmittals needed for changes to one line; mount detector at top of stair; need record of completion 1/8/2004 11:14:56 AM
INSP-Conference12/15/200312/16/200312/16/2003APART
DetailsRick Jackson
Jim; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes met with GC and electrical contractor about pull stations in condo units - they aren't shown on approved plans and not required 12/16/2003 10:12:39 AM