INSP-Final Inspection | 12/11/2003 | 12/11/2003 | 12/11/2003 | P | PASS |
Rick Jackson
|
|
|
|
INSP-Alarm Testing | 12/10/2003 | 12/10/2003 | 12/10/2003 | P | CANC |
Troy Cobbley
|
|
|
Scott said that they would like to reschedule for tomorrow with the alarm inspection. I told him to call it in 12/10/2003 10:41:38 AM
|
INSP-Final Inspection | 12/5/2003 | 12/5/2003 | 12/5/2003 | P | FAIL |
Troy Cobbley
|
|
|
Provide pendant outside of laundry room and supply required pump information to Bill Alexander for approval 12/5/2003 1:38:18 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2003 | 12/1/2003 | 12/1/2003 | P | CANC |
Troy Cobbley
|
|
|
Please call about 1 hour prior to arrival.; Phone #: ###-#### Internet Inspection Request from: Trent Bice
|
INSP-Sprinkler Rough-in/Hydro | 11/20/2003 | 11/20/2003 | 11/20/2003 | P | PART |
Troy Cobbley
|
|
|
sprinkler piping in attic appears to be properly tented. I notified the contractor (Trent Bice) that the insulation would have to be brought up over the tenting and the pipe to prevent freezing 11/20/2003 4:30:58 PM
|
INSP-Sprinkler Rough-in/Hydro | 8/18/2003 | 8/19/2003 | 8/19/2003 | P | FAIL |
Troy Cobbley
|
|
|
No items on the correction notice have been completed. The insulation contractor blew in the attic insulation with out tenting the sprinkler piping. Shilo to provide up to date cpvc sprinkler pipe hanger data 8/19/2003 3:42:58 PM
|
INSP-Sprinkler Rough-in | 8/6/2003 | 8/7/2003 | 8/7/2003 | A | FAIL |
Troy Cobbley
|
|
|
tate; Phone #: ###-#### Provide updated fire sprinkler drawings to the city with a floor plan that matches the actual wall layout and sprinkler piping layout. Pendant is missing a hanger in closet in east side of the building. In the same location piping is attached to wood supprt that is not completly attached to the trusses. All existing insulation needs to be removed from below the sprinkler piping. Provide access and ladder so all piping can be inspected. Provide tenting for sprinkler piping per approved plans and nfpa 13d with access for inspection 8/7/2003 3:21:54 PM
|
FIR-Aging Inspection | 6/9/2003 | 6/9/2003 | 6/9/2003 | | NR |
Troy Cobbley
|
|
|
I spoke to Bob Knight with Shilo and he stated that the contractor is not ready for them to start work yet. 6/9/2003 10:43:55 AM
|