INSP-Final Inspection | 10/21/2003 | 10/22/2003 | 10/22/2003 | A | PASS |
Troy Cobbley
|
|
|
Peter; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
|
INSP-Final Inspection | 4/28/2003 | 4/30/2003 | 4/30/2003 | A | FAIL |
Troy Cobbley
|
|
|
Provide map, signals that arrive at the monitoring company do not match the signals sent. All zones existing and new need verified to match. The supposed duct detector zone came in as a refrigerent trouble 4/30/2003 4:05:29 PM
|
INSP-Final Inspection | 4/28/2003 | 4/29/2003 | 4/29/2003 | A | CANC |
Rick Jackson
|
|
|
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 3/14/2003 | 3/17/2003 | 3/17/2003 | A | FAIL |
Troy Cobbley
|
|
|
Test south duct detector, Provide 60 hour battery backup per review note #7. The actual standby current draw is 400Ma which requires 28.8 AH batteries. Existing duct detector zone is labeled tamper/supervisory, relabel for the devices, provide map per review note #4, mount smoke detector on deck, provide dedicated circuit per review note #11 and as stated on the plans, verify signals 3/17/2003 11:16:10 AM
|