Description
To supervise two new duct smoke detectors in the new tenant space. The detectors are to be connected to an existing fire alarm system.
The associated building permit (BLD 02-03048) is to remodel an existing 4,806 square foot tenant space for an existing tenant. This tenant space is located in a 288,657 square foot, one story, retail sales strip mall shopping center. Work is to include a restroom accessible to the disabled, a new landing at the main entrance doors (South wall), new doors in an existing opening in the North wall, a new landing at the new doors, and new lay-in ceiling tile all per approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13 as regulated by the Fire Department.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/21/200310/22/200310/22/2003APASS
DetailsTroy Cobbley
Peter; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes
INSP-Final Inspection4/28/20034/30/20034/30/2003AFAIL
DetailsTroy Cobbley
Provide map, signals that arrive at the monitoring company do not match the signals sent. All zones existing and new need verified to match. The supposed duct detector zone came in as a refrigerent trouble 4/30/2003 4:05:29 PM
INSP-Final Inspection4/28/20034/29/20034/29/2003ACANC
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
INSP-Final Inspection3/14/20033/17/20033/17/2003AFAIL
DetailsTroy Cobbley
Test south duct detector, Provide 60 hour battery backup per review note #7. The actual standby current draw is 400Ma which requires 28.8 AH batteries. Existing duct detector zone is labeled tamper/supervisory, relabel for the devices, provide map per review note #4, mount smoke detector on deck, provide dedicated circuit per review note #11 and as stated on the plans, verify signals 3/17/2003 11:16:10 AM