Permit Information
Permit NumberFIR03-00087
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 5550 W MORRIS HILL RD
Project NameSPR CNTY MORGUE OFFICES
Customer Number 
ePlanReview 
Description
(ADA COUNTY CORONER - MORGUE) To install fire sprinkler protection in approximately 1,735 ft/2 area of rest rooms and administrative offices on the 1st floor and 2,385 ft/2 area of rest rooms and administrative offices on the 2nd floor within an existing 24,000 square foot warehouse/office building used by the Ada County Coroner's Office per approved drawings, engineering, and plan review conditions on file. This building is fire sprinklered for area increase. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This is work required to meet Fire Department requirements for Fire Code occupancy compliance (Upgrade Agreement letter on file dated 8/22/02). This permit is not attached to a building permit.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/20/20036/20/20036/20/2003PPASS
DetailsTroy Cobbley
fire sprinklers finaled 6/20/2003 1:43:48 PM
INSP-Sprinkler Rough-in4/16/20034/16/20034/16/2003PFAIL
DetailsTroy Cobbley
Provide fire caulking at the 2" penatration into the warehouse, provide the correct QR pendant in the 2nd floor office and provide the 4 way EQ bracing on the second floor main just before the wall penatration into the warehouse
INSP-Sprinkler Rough-in/Hydro4/16/20034/16/20034/16/2003PFAIL
DetailsTroy Cobbley
Provide city approved resubmitted plans showing all the piping changes. This deficiancy need to be added to the other inspection report for this project for this day
INSP-Sprinkler Rough-in/Hydro4/14/20034/16/20034/16/2003APART
DetailsTroy Cobbley
john ###-#### Hydro test for the second and third floors is OK. But items on correction notices still need corrected 4/16/2003 3:32:17 PM