Permit NumberFIR03-00104
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 190 E FRONT ST
Project Namealm-COURTHOUSE-PA3 APARTMENTS
Customer Number 
ePlanReview 
Description
CIVIC PLAZA PA-3 APARTMENTS - This permit is to install a new manual fire alarm system and single/multiple station smoke detection in dwelling units, as part of the construction of the R-1 apartment building. The new alarm system will cover the existing 3-story and basement parking structure and the new 4-story apartment and retail building. The manual alarm system includes pull stations at all exits, audible alarms in all building areas, visual annunciation in common and public use areas and hearing impaired dwelling units, elevator recall functions, and monitoring of the fire sprinkler system and fire pump.
The associated building permit (BLD 02-00090) is to construct a 152 unit, 4-levels of R-1 apartments on an existing three story, Type S-3 parking garage with a grade level leasing office and community center laundry room and storage facility for the apartment complex. Work to include landscaping spine and temporary (grade) parking lot. * PLAN MODIFICATION * Change exterior curtain walls to standard walls, with openable windows and grills over A/C units, remodel first floor leasing office space, move fire pump room and emergency generator room, install PTAC units in each habitable room.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/31/200312/31/200312/31/2003PPASS
DetailsRick Jackson
INSP-Final Inspection9/30/200310/1/200310/1/2003AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 9/30/2003 at 5:48:12 PM. Contact: ###-####. need updated maps; verify all covers are off the smoke detectors 10/1/2003 12:48:51 PM
INSP-Alarm Testing9/29/20039/29/20039/29/2003APART
DetailsRick Jackson
tested all exsisting sprinkler control tampers and flows- okay; tested new residential tampers and flows - okay; still need to verify phase reversal for fire pump
INSP-Alarm Testing9/25/20039/26/20039/26/2003AFAIL
DetailsRick Jackson
smoke detectors need to be within 12 inches of deck in stairs and elevator machine room; need heat detectors added in elevator machine rooms; descriptor for first floor NAC detector and location has changed to update map also; need to test elevator recall and all flows and tampers; reverify phase reversal on fire pump; batteries not supervised; strobes in ADA sleeping rooms within 24 inches to be 177cd or lower strobe; need circuit breaker location on NAC's with lockout; tested location of devices on all living floors -okay; tested notification devices on all living floors - okay except ADA rooms; need updated maps and NFPA 72 forms when complete 9/26/2003 12:10:45 PM
INSP-Final Inspection9/25/20039/25/20039/25/2003PFAIL
DetailsRick Jackson
started testing alarms - detectors within 3 ft of diffusers; fire pump controller not reporting phase reversal and showed pump running when pump wasn't running; phone line not reporting trouble; need special function buttons labeled; batteries not reporing troubles; will need to test devices and all exsisting sprinkler valves; need maps; will continue testing on 9/26 9/25/2003 4:13:57 PM
INSP-Sprinkler Rough-in/Hydro7/1/20037/3/20037/3/2003PPART
DetailsRick Jackson
Could the inspection be scheduled at
1:30 pm.; Phone #: ###-#### Internet Inspection Request from: Paul Highley alarms are okay on first floor operations area only 7/3/2003 2:54:31 PM