INSP-Final Inspection | 12/31/2003 | 12/31/2003 | 12/31/2003 | P | PASS |
Rick Jackson
|
|
|
|
INSP-Final Inspection | 9/30/2003 | 10/1/2003 | 10/1/2003 | A | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/30/2003 at 5:48:12 PM. Contact: ###-####. need updated maps; verify all covers are off the smoke detectors 10/1/2003 12:48:51 PM
|
INSP-Alarm Testing | 9/29/2003 | 9/29/2003 | 9/29/2003 | A | PART |
Rick Jackson
|
|
|
tested all exsisting sprinkler control tampers and flows- okay; tested new residential tampers and flows - okay; still need to verify phase reversal for fire pump
|
INSP-Alarm Testing | 9/25/2003 | 9/26/2003 | 9/26/2003 | A | FAIL |
Rick Jackson
|
|
|
smoke detectors need to be within 12 inches of deck in stairs and elevator machine room; need heat detectors added in elevator machine rooms; descriptor for first floor NAC detector and location has changed to update map also; need to test elevator recall and all flows and tampers; reverify phase reversal on fire pump; batteries not supervised; strobes in ADA sleeping rooms within 24 inches to be 177cd or lower strobe; need circuit breaker location on NAC's with lockout; tested location of devices on all living floors -okay; tested notification devices on all living floors - okay except ADA rooms; need updated maps and NFPA 72 forms when complete 9/26/2003 12:10:45 PM
|
INSP-Final Inspection | 9/25/2003 | 9/25/2003 | 9/25/2003 | P | FAIL |
Rick Jackson
|
|
|
started testing alarms - detectors within 3 ft of diffusers; fire pump controller not reporting phase reversal and showed pump running when pump wasn't running; phone line not reporting trouble; need special function buttons labeled; batteries not reporing troubles; will need to test devices and all exsisting sprinkler valves; need maps; will continue testing on 9/26 9/25/2003 4:13:57 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/1/2003 | 7/3/2003 | 7/3/2003 | P | PART |
Rick Jackson
|
|
|
Could the inspection be scheduled at
1:30 pm.; Phone #: ###-#### Internet Inspection Request from: Paul Highley alarms are okay on first floor operations area only 7/3/2003 2:54:31 PM
|