Permit Information
Permit NumberFIR03-00123
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 2288 N GARDEN ST
Project NameSPR JOE'S CRAB SHACK
Customer Number 
ePlanReview 
Description
(JOE'S CRAB SHACK) To modify an existing fire sprinkler system in a 6,943-ft/2 remodel for a restaurant (new owner-originally the Chart House). Work is related to a complete interior remodel, construction of a new canopy over entrance, new type-1 hood and grease duct shaft, remove stairs from second floor loft and new mechanical loft with a permanent access ladder. This building is fully fire sprinklered for one-hour fire-resistive construction. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-003091.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection9/28/20059/28/20059/28/2005APASS
DetailsForrest France
Additional pump flow test performed with Jim Danes of DeBest fire, 100% and 150% rated flow verified with residual pressure at 100% satisfactory.
INSP-Final Inspection11/15/200411/16/200411/16/2004AFAIL
DetailsRick Jackson
Fire Pump Final - Contact Brian - would like to have scheduled at 9 am; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Pump test at 150 percent resulted in negative pressure on suction side of pump; Sam Rogers recorded all pump test data 11/16/2004 10:24:33 AM
INSP-Final Inspection8/19/20038/21/20038/20/2003AFAIL
DetailsRick Jackson
jim--fn with a fire pump; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Need fire pump data and jockey/fire pump controller test lines to drain; fire pump couldn't pump to 150 percent capacity as the suction was at zero. 8/21/2003 7:25:53 AM
INSP-Sprinkler Rough-in/Hydro7/7/20037/7/20037/7/2003PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 7/7/2003 at 10:45:26 AM. Contact: ###-####. wet and antifreeze systems will require annual inspection; heads overspaced above ceiling in kitchen per plan review notes; mezzanine area not fully sprinklered; head obstructed by partition in mens room; remove paper from heads throughout; sprinklers or noncumbustible area by dishwasher along wall; repair head in storage room; submit data for fire pump to plan review 7/7/2003 3:38:26 PM