Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR03-00128
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 6805 07 W BARON AVE
Project NameSPR IRENE VICTORY DUPLEX
Customer Number 
ePlanReview 
Description
(IRENE VICTORY DUPLEX) This 2,524-ft/2 DUPLEX structure requires to be fitted with a 13D-1999, fire sprinkler system. Each unit is a two story, three bedrooms, 1¾" bathroom with 1,262-ft/2 floors. This structure is being build to only meet duplex standards and not to be sold as individual units. The fire sprinkler flow alarm shall be interconnected to the required residence smoke detection system. All fire sprinkler work and related, which includes single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments, under direction of the Fire Chief. This permit is attached to: BLD02-00254
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/1/20037/2/20037/2/2003PPASS
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 7/1/2003 at 2:15:49 PM. Contact: ###-####.
INSP-Final Inspection7/1/20037/1/20037/1/2003PFAIL
DetailsTroy Cobbley
provide locks on the valves per the plan review notes and test flow switches 7/1/2003 3:34:41 PM
INSP-Final Inspection6/26/20036/27/20036/27/2003PFAIL
DetailsTroy Cobbley
Provide additional 175 pendants for the head box, provide the correct orfice in the inspectors test, provide steel pipe and standard pendant in the furnace room, flush underground, lock valves, replace painted pendants, pendant in the kitchen is blocked by a surface mounted light 6/27/2003 1:39:35 PM
INSP-Sprinkler Rough-in/Hydro6/19/20036/20/20036/20/2003ACANC
DetailsTroy Cobbley
wrong inspection called in per Mike with Debest. This job is not ready yet 6/20/2003 8:50:03 AM
INSP-Sprinkler Rough-in5/12/20035/13/20035/13/2003APASS
DetailsTroy Cobbley
Fire sprinkler piping is OK to cover. I notified John Venchie with Debest Fire Protection that on the second floor in both apartments that the tenting on the pipe could be improved in a couple of locations. He stated that it would be taken care of. I also said the same thing to Frank, the superintendant 5/13/2003 9:17:19 AM 5/13/2003 9:20:22 AM
INSP-Sprinkler Rough-in5/6/20035/6/20035/6/2003PFAIL
DetailsTroy Cobbley
The sprinkler piping and risers as installed do not match the approved plans. Resubmit plans that show as-built information. Do not cover pipe until plans have been approved and reinspected. A do not cover sticker was left at project. The east side second floor apartment plan shows 1 1/2 pipe to be installed. 1" is installed. Could not verify piping per notes #5, #6 and #7. Per review note #8 1 1/2 pipe is to be installed but 1 1/4 is installed. Resubmitt calculations. No other items inspected 5/6/2003 2:59:50 PM