Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberFIR03-00153
StatusFinaled
Name SYNERGY ENGINEERS
Site Address 252 E FRONT ST
Project Namealm ID WATER CENTER-PA2 BLDG A
Customer Number 
ePlanReview 
Description
CIVIC PLAZA PA-2 APARTMENTS-This permit is to install a new manual fire alarm system and single/multiple station smoke detection in dwelling units, as part of the construction of the R-1 apartment building. The new alarm system will cover the basement parking structure ground floor parking area and the 5-story apartment building. The manual alarm system includes pull stations at all exits, audible alarms in all building areas, visual annunciation in common and public use areas and hearing impaired dwelling units, elevator recall functions, and monitoring of the fire sprinkler system and fire pump.
There are separate permits and a Certificate of Occupancy required to finish and occupy each future tenant space.
The associated building permits are:
BLD 02-00369 (shell & core) - To construct a new 30,873 sq. ft. parking garage and retail sales area, with a three hour occupancy separation per UBC Section 311.2.2.1, on top of an existing Type I-FR. underground parking structure. To complete center core, restroom and laundry facilities for the upper floor apartments. The parking area is 9,300 sq. ft. and there is 12,600 sq. ft. for future tenant space.
BLD02-00370 (Section 1 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 25 units, @ 3,869 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00371 (Section 2 of 6) To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 25 units, @ 4,767 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00372 (Section 3 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 20 units, @ 4,413 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00373 (Section 4 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 25 units, @ 4,666 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00374 (Section 5 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 20 units, @ 3,866 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
BLD02-00375 (Section 6 of 6) - To construct two four-hour area separation walls to divide this building into six separate buildings. This section is 5 stories and 29 units, @ 4,180 sq.ft. per floor, above a three-hour occupancy separation per UBC Section 311.2.2.1.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/24/20042/24/20042/24/2004PPASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/24/2004 at 8:20:12 AM. Contact: ###-####.
INSP-Final Inspection2/23/20042/23/20042/23/2004PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/23/2004 at 11:06:48 AM. Contact: ###-####. need updated map as in-duct adresses have changed from plans; horn not working by room 303; floor designations on maps not correct and missing 2nd floor 2/23/2004 4:56:04 PM
INSP-Final Inspection2/19/20042/20/20042/20/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/19/2004 at 3:54:18 PM. Contact: ###-####. contractor hasn't completed testing 2/20/2004 4:22:06 PM
INSP-Final Inspection2/17/20042/19/20042/19/2004AFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 2/17/2004 at 6:22:16 PM. Contact: ###-####. strobes not within 15 ft from ends of corridors; need to test devices/notification 2/19/2004 3:46:25 PM
INSP-Alarm Testing1/5/20041/6/20041/6/2004ANR
DetailsRick Jackson
mark 208/941/1847
FIR-Aging Inspection8/26/20038/26/20038/26/2003 PASS
DetailsRick Jackson
the building is still under construction 8/26/2003 7:46:13 AM