Description
8/29/2003 - Fire alarm scope is to disconnect the inputs from zones 14 and 15 (deluge zones no longer required) and to connect a duct smoke detector and ansul cooking hood. Notification devices will require upgrade in the TI space only.

The associated building permit (BLD 02-01179) is to remodel an existing 1146 sq ft retail tenant space to create a new restaurant tenant space per approved plans on file. Work to include, Installation of new type one hood system and new one hour grease duct shaft, installation of new service counter, kitchen appliances, new plumbing work, and miscellaneous related interior finishes. Note: This building is fully fire sprinklered for 1-hr. fire resistive substitution. Any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (PC#315-02) rmh
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/200311/18/200311/18/2003PPASS
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Robert Bailey
INSP-Alarm Testing10/29/200310/31/200310/31/2003AFAIL
DetailsTroy Cobbley
The new battery cabinet still does not report to the facp when the batteries have been disconnected. All other items and devices tested ok 10/31/2003 10:21:17 AM
INSP-Final Inspection10/14/200310/15/200310/15/2003PCANC
DetailsTroy Cobbley
Would like inspection for 2:00pm, Simplex Grinnell will be onsite for their final at this time; Phone #: ###-#### Internet Inspection Request from: Robert Bailey
INSP-Final Inspection10/14/200310/15/200310/15/2003PFAIL
DetailsTroy Cobbley
Provide map per note #17, provide breaker lock on the main breaker, the new battery charger and the existing NAC panel do not report a trouble at the main facp panel nor at the central station. Grinnell did not show up for their part of the test. No devices have been tested10/15/2003 3:36:28 PM 10/15/2003 3:37:47 PM