Permit Information
Permit NumberFIR03-00174
StatusFinaled
Name SHILO AUTOMATIC SPRINKLER CO
Site Address 1673 W SHORELINE DR
Project NameSPR Riverwalk Center Shell
Customer Number 
ePlanReview 
Description
Riverwalk Center ( Shell & Core) - To install a new fire sprinkler system in a new 20,570-ft/2, two story shell and core building. This building is constructed of steel structural frame, some precast concrete and concrete masonry walls, steel joists. The core work includes restrooms, corridors, stairways, elevator and mechanical rooms. This is a shell and core permit only and no occupancy is approved under this permit. Separate fire permits required for improvements to finish this building for occupancy. This building is fully fire sprinklered. The fire sprinkler system work shall comply with NFPA 13-1999, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD02-02687.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/1/20038/1/20038/1/2003PPASS
DetailsRick Jackson
INSP-Final Inspection7/30/20037/30/20037/30/2003AFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Trent Bice need one hour fire sprinkler riser room; ball drip on FDC; additional EQ on FDC; spare heads in head box; calc sticker; fire marshall tag on riser; sign on riser room door; escutcheons; some heads obstructed; straps needed; 7/30/2003 11:46:45 AM
INSP-Sprinkler Rough-in/Hydro7/23/20037/24/20037/24/2003APART
DetailsTroy Cobbley
above ground hydro test ok after 2nd try 7/24/2003 2:40:52 PM
INSP-Sprinkler Rough-in/Hydro5/19/20035/19/20035/19/2003PPART
DetailsRick Jackson
This is for your walkthrough that you performed on friday; Phone #: ###-#### Internet Inspection Request from: Trent Bice flange fitting at UG connection to meet NFPA 13 Table 3-5.1; r/i okay 5/19/2003 12:25:57 PM