INSP-Final Inspection | 10/1/2003 | 10/2/2003 | 10/2/2003 | A | PASS |
Rick Jackson
|
|
|
This is Bobs # from Lea Electric; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
INSP-Final Inspection | 9/30/2003 | 9/30/2003 | 9/30/2003 | P | FAIL |
Troy Cobbley
|
|
|
fire alarm signals are still not being reported correctly or the monitoring company does not know what they are doing. 9/30/2003 3:52:04 PM
|
INSP-Final Inspection | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | FAIL |
Troy Cobbley
|
|
|
The monitoring company had the account messed up. No inspection performed 9/26/2003 3:19:11 PM
|
INSP-Final Inspection | 9/23/2003 | 9/24/2003 | 9/24/2003 | A | NR |
Rick Jackson
|
|
|
This is Grants Cell Have a great Afternoon; Phone #: ###-#### Internet Inspection Request from: Terry Owsley 9/24/2003 9:46:03 AM
|
INSP-Final Inspection | 9/24/2003 | 9/24/2003 | 9/24/2003 | P | FAIL |
Troy Cobbley
|
|
|
duct detector signals arrive at the monitoring station as gatevavles, pull in lobby comes in as pull - fire, smoke in lobby comes in as general alarm, update the map to show the duct detectors, verify that the 8521 address is reported separatly 9/24/2003 2:54:13 PM
|
INSP-Final Inspection | 9/4/2003 | 9/5/2003 | 9/5/2003 | A | FAIL |
Troy Cobbley
|
|
|
Inspection was for the clubhouse. Duct smoke detectors need to be provided. Review notes have not been followed. I stopped the inspection. Inspection to be called in after verifying all comments have been addressed 9/5/2003 2:15:25 PM
|