Permit Information
Permit NumberFIR03-00258
StatusFinaled
Name NORTHWEST SALES COMPANY
Site Address 7960 W NORTHVIEW ST
Project NamealmSt Marks Catholic Community
Customer Number 
ePlanReview 
Description
New fire alarm system in new structure, fully sprinklered.

1/28/2004 - Additional scope, three strobes were required per the PDS Fire Inspector.

There is no impact to the battery, voltage drop and speaker wattage calculations, existing batteries are acceptable.


12/11/2003 - Additional scope, the following is being installed in area A (see modified plans, items are clouded):
" one new duct detector for HVAC shutdown (RTU-7)
" three new strobes to cover new space
" three new in-duct detectors for fire/smoke damper control
" two new pull stations
" four relocated strobes
" two relocated pull stations

There is no impact to the battery, voltage drop and speaker wattage calculations, existing batteries are acceptable.

12/16/2003 - Received updated matrix to include the in-duct detector for HVAC shutdown. Revised matrix is in the packet.

The associated building permit (BLD 02-02454) is to construct a new 26,050 sq.ft. single story, sanctuary, restroom and entry vestibule. NOTE: This building is fully fire sprinklered for one-hour substitution. This permit includes if accepted alternate #2 to "Area A", demo entry, modify existing exterior wall and make a two-hour separation wall and connect "Area A & Area B" via an new entry lobby. All construction per the approved plans and attached comment list. Refer to BLD 02-02667 for remodel of Area "A". See BLD 02 -02236 for grading permit. MJP PC#652-02 CUP02-00038
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/26/20047/26/20047/26/2004PPASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection1/21/20041/21/20041/21/2004APASS
DetailsTroy Cobbley
INSP-Alarm Testing1/15/20041/16/20041/16/2004PFAIL
DetailsTroy Cobbley
Demo old fire alarm system, 185cd a/v's in room A38 are oerspaced. They exceed 35' from the walls. Provide strobe coverage in A38 mezzanine. Provide strobe in corridor behind A37. Provide strobe in unmarked toilet north of A27. Provide strobe in toilet A28. Resubmit plans per review note #2. 1/16/2004 3:06:49 PM
INSP-Alarm Testing12/22/200312/23/200312/23/2003PPART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers permission until the existing building is completed. Battery calcs, map, breaker locks and breaker box location. Existing building needs to be inspected 12/23/2003 1:23:42 PM
FIR-Aging Inspection10/20/200310/20/200310/20/2003 NR
DetailsTroy Cobbley
work in progress 10/20/2003 3:27:34 PM