INSP-Final Inspection | 6/9/2004 | 6/14/2004 | 6/14/2004 | A | PASS |
Rick Jackson
|
|
|
clifford; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
INSP-Final Inspection | 5/25/2004 | 5/28/2004 | 5/28/2004 | A | FAIL |
Rick Jackson
|
|
|
CLIFFORD; Phone #: ###-#### Internet Inspection Request from: Annette Moore On fire alarm NAC panel #1 circuits 1-2 develpoe a trouble condition that won't clear without powering down panel 5/28/2004 9:54:15 AM
|
INSP-Final Inspection | 5/18/2004 | 5/24/2004 | 5/24/2004 | A | FAIL |
Rick Jackson
|
|
|
Clifford; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Trouble on NAC-1 circuit - 2; descriptor for NAC/EVAC trouble modules; water flow restores alarm when flow stops 5/24/2004 10:32:22 AM
|
INSP-Conference | 3/22/2004 | 3/22/2004 | 3/22/2004 | A | DONE |
Troy Cobbley
|
|
|
I called to speak to Cliff but was only able to leave a message. I need description on what the scope of work is since this project was just issued.
|
INSP-Final Inspection | 2/24/2004 | 3/1/2004 | 3/1/2004 | A | FAIL |
Rick Jackson
|
|
|
cliff-- ###-#### need resubmittals as there are two SNAC panels instead of one - 4 NAC are one SNAC and NAC 7-8 are on the other; batteries on SNAC aren't supervised; speakers are T-tapped; need maps; spot checked several smokes but need to test for alarm; need to check FACP for troubles; strobe to be 95 cd instead of 75 in SW gallery (see plans); need to test smokes for alarms and tampers plus manaul pulls and duct detectors; detectors 52 -and 53 are actually 72 and 74 - update maps/plans(didn't show up on address list either 3/1/2004 6:09:07 PM
|
INSP-Final Inspection | 2/23/2004 | 2/24/2004 | 2/24/2004 | A | NR |
Rick Jackson
|
|
|
CLIFF; Phone #: ###-#### Internet Inspection Request from: Darla Downs rescheduled for 34/1/04 2/24/2004 8:41:10 AM
|
INSP-Final Inspection | 8/5/2003 | 8/6/2003 | 8/6/2003 | A | CANC |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 8/5/2003 at 9:53:09 AM. Contact: ###-####. this permit was called in by mistake by another contractor 8/6/2003 9:52:32 AM
|
INSP-Final Inspection | 8/6/2003 | 8/6/2003 | 8/6/2003 | P | CANC |
Rick Jackson
|
|
|
wrong permit added by inspector 409 8/6/2003 11:06:51 AM
|