INSP-Final Inspection | 12/12/2003 | 12/12/2003 | 12/12/2003 | P | PASS |
Rick Jackson
|
|
|
|
INSP-Final Inspection | 12/10/2003 | 12/10/2003 | 12/10/2003 | A | FAIL |
Rick Jackson
|
|
|
escutcheons needed/remove tape on heads; need signage on drains; need hanger on pipe in mechanical room 12/10/2003 11:23:21 AM
|
INSP-Sprinkler Rough-in/Hydro | 12/8/2003 | 12/8/2003 | 12/8/2003 | P | FAIL |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/8/2003 at 7:42:59 AM. hydro on new system okay; will need drain signage; need hanger on branch line in mechanical near kitchen; tie-in not complete and will verify at final;need escutcheons 12/8/2003 4:19:50 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2003 | 12/2/2003 | 12/2/2003 | A | NR |
Rick Jackson
|
|
|
never received call from Moke that the hydro test was ready 12/3/2003 1:40:34 PM
|
INSP-Sprinkler Rough-in/Hydro | 12/1/2003 | 12/1/2003 | 12/1/2003 | P | NR |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 12/1/2003 at 11:00:54 AM. Contact: ###-####. rescheduled for 12/2/03 12/1/2003 4:04:11 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/6/2003 | 11/7/2003 | 11/7/2003 | A | PART |
Rick Jackson
|
|
|
11 am - air test end - 49 psi air test okay; need head in closet by entryway; tenting in progress for return bend and will be completed before insulating 11/7/2003 1:59:04 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/5/2003 | 11/6/2003 | 11/6/2003 | A | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 11/5/2003 at 3:20:54 PM. Contact: ###-####. start air test 49 psi at 11 am 11/6/2003 12:33:57 PM
|
INSP-Sprinkler Rough-in/Hydro | 10/23/2003 | 10/24/2003 | 10/24/2003 | P | FAIL |
Rick Jackson
|
|
|
stop air test stopped by the job site to talk to the GC and checked the gauge - is at 22 psi. 10/24/2003 10:34:02 AM
|
INSP-Sprinkler Rough-in/Hydro | 10/23/2003 | 10/23/2003 | 10/23/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 10/23/2003 at 9:41:19 AM. start air test at 42 psi 10/23/2003 3:40:54 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/19/2003 | 9/19/2003 | 9/19/2003 | P | CANC |
Troy Cobbley
|
|
|
Inspection was for 24 hour air test for the dry pipe system. Contractor wanted a witness for the finish of the test. I told them someone needed to witness the start of the test. They will do it over starting monday 9/19/2003 4:17:34 PM
|
INSP-Sprinkler Rough-in | 9/11/2003 | 9/12/2003 | 9/12/2003 | P | PART |
Rick Jackson
|
|
|
checked status of tenting and nothing has changed since yesterday 9/12/2003 3:22:10 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/11/2003 | 9/11/2003 | 9/11/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/11/2003 at 8:45:47 AM. Contact: ###-####. tenting has started and the areas started are going good; middle area of south side okay for rough-in 9/11/2003 2:25:24 PM
|
INSP-Sprinkler Rough-in/Hydro | 9/8/2003 | 9/8/2003 | 9/8/2003 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 9/8/2003 at 9:30:32 AM. Contact: ###-####. okay to cover northwest side of new addition 9/8/2003 4:06:24 PM
|
INSP-Sprinkler Rough-in | 9/4/2003 | 9/5/2003 | 9/5/2003 | P | FAIL |
Rick Jackson
|
|
|
ross; Phone #: ###-#### Internet Inspection Request from: Barbara Moore attic heads overspaced in classrooms; attic heads not 16-22 inches drom ridge; deflector on hip heads turned the wrong way; sprigs not supported; attic area not protected in north side room; heads within 6 ft in rooms with moveable partitions; return bends not used in all areas; area under stairs and under stage require sprinkler protection; FDC obstrcuted by bushes; not approved for cover 9/5/2003 4:23:11 PM
|