Permit Information
Permit NumberFIR03-00375
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 601 N PHILLIPPI ST
Project NameSPR STEIN DISTRIBUTING
Customer Number 
ePlanReview 
Description
(STEIN DISTRIBUTING CO., INC.) To install wet pipe fire sprinkler protection into the remodeled 1,768-ft/2 and expanded 1,768-ft/2 two-story office areas, located within an existing warehouse, for a total of 3536-ft/2. Work is related to include new walls around new the portion and upgrading walls and openings around existing office area to separate the office area from the warehouse with two-hour fire barrier walls. Includes a new vertical exit enclosure from second floor area, the removal and rebuilding of stairs on lower level, which access the warehouse area. This building is partially sprinklered for High Piled Storage use with a letter on file, to fully sprinkler the building by 2006. All fire sprinklers and related appurtenance within this permit work scope shall meet current NFPA 13-1999 standards, comply with the IFC-2000 and attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, in order to provide witness verification of compliance in meeting minimum code standards. This permit is attached to building permit: BLD03-00657.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection4/20/20044/20/20044/20/2004APASS
DetailsTroy Cobbley
Fire alarm finaled on 1/8/2004 under FIR03-00658
INSP-Final Inspection11/10/200311/10/200311/10/2003APART
DetailsTroy Cobbley
Temp occupancy given until the fire alarm system has been approved, installed and tested per Dave Millers permission
INSP-Sprinkler Rough-in/Hydro10/30/200310/31/200310/31/2003APASS
DetailsTroy Cobbley
wet system hydro test is ok 10/31/2003 1:49:46 PM
INSP-Sprinkler Rough-in/Hydro10/23/200310/24/200310/24/2003APART
DetailsTroy Cobbley
rough-in items from the first two inspections have been taken care of. Items at the riser still need to be completed. Hydro test failed. 10/24/2003 1:02:37 PM
INSP-Sprinkler Rough-in/Hydro10/6/200310/7/200310/7/2003PPART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/6/2003 at 1:41:13 PM. Contact: ###-####. okay to cover 2nd floor only except room 209 as it has protective cover on head; the branch line on the north side of the new addition is not installed; the new wet part of the riser is not complete; canopies not installed on all 401 heads; will need spare heads in head box; branch line on east side not complete; this building will now have over 20 heads and will require monitoring and does not have complete sprinkler coverage 10/7/2003 3:24:35 PM
INSP-Sprinkler Rough-in/Hydro10/1/200310/2/200310/2/2003APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 10/1/2003 at 2:01:10 PM. area on first floor okay to cover except by the NE area by stair as SSU and SSP are too close together - reinspection needed to cover this area; sidewall installed under stair instead of pendant as shown on plans 10/2/2003 9:52:07 AM