Permit NumberFIR03-00399
StatusFinaled
Name THE SECURITY GROUP
Site Address 12601 W EXPLORER DR Unit: 250
Project Namealm - ZASIO-2ND FLR
Customer Number 
ePlanReview 
Description
The addition of 19 duct detectors, 12 fire/smoke dampers with associated in-duct smoke detectors and one notification device to an existing sprinkler monitoring fire alarm system with HVAC shutdown and elevator recall.

The associated building permit (BLD 02-02987) is to construct a 8,842 square foot office tenant space located on the 22,000 square foot 2nd floor of a 44,000 square foot, 2 story, building. Work is to included tenant demising walls, a restroom accessible to the disabled, interior nonbearing walls, interior finishes, interior doors and windows, and suspended ceilings all per approved drawings and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. (ZASIO - SUITE 250) This building is fire sprinklered for building area increase. **CJW**

The associated building permit (BLD 02-02988) is to construct a 5,375 square foot office tenant space located on the 22,000 square foot 2nd floor of a 44,000 square foot, 2 story, building. Work is to included tenant demising walls, interior nonbearing walls, interior finishes, interior doors, and suspended ceilings all per approved drawings and plan review conditions on file. The fire sprinkler system shall comply with NFPA 13 as regulated by the Fire Department. (BRIGHTON CORPORATION - SUITE 200) This building is fire sprinklered for building area increase. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection8/22/20038/22/20038/22/2003PPASS
DetailsTroy Cobbley
INSP-Alarm Testing8/20/20038/21/20038/21/2003ACANC
DetailsTroy Cobbley
technical problems with the induct detector circuit 8/21/2003 3:36:25 PM
INSP-Final Inspection8/13/20038/14/20038/14/2003PFAIL
DetailsTroy Cobbley
mike; Phone #: ###-#### The sample tube duct smoke detectors that are being used for smoke damper operation are not listed for use on the 8" round duct, provide access to all dampers, test power supervision for the elevator, test the two duct smoke detectors being used for damper operation at the entrance to suite 200. All items tested are listed on the approved plans 8/14/2003 4:36:57 PM
INSP-Alarm Testing8/12/20038/13/20038/13/2003PCANC
DetailsRick Jackson
Scheduled by a contractor via Hello! on 8/12/2003 at 2:34:17 PM. Contact: ###-####. rescheduled for 8/14 as I was delayed on another permit 8/13/2003 5:22:28 PM