Permit Information
Permit NumberFIR03-00403
StatusFinaled
Name WESTERN FIRE PROTECTION INC
Site Address 1346 S ORCHARD ST
Project NameSPR UG ORCHARD CENTER MALL
Customer Number 
ePlanReview 
Description
(ORCHARD CENTER MALL - UNDERGROUND) To install approximately 75'-0" of 6" C-900 PVC from the property line in Clark Street, north and then west under the footing and with 6" D.I. Class 50, up through the floor within an existing 20,370-ft/2 building for IBC allowable area increase under BLD03-01739. The fire sprinkler underground installation work shall comply with NFPA 13-1999, NFPA 24-1995 and the UFC-1997, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. OH fire sprinkler system permit is submitted under FIR03-00390. This permit is attached to building permit: BLD03-01810.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection11/17/200311/17/200311/17/2003PPASS
DetailsTroy Cobbley
INSP-Sprinkler Rough-in/Hydro10/2/200310/3/200310/3/2003PPART
DetailsRick Jackson
harry; Phone #: ###-#### Internet Inspection Request from: Barbara Moore hydro on overhead okay; forward flow of the BFP okay; need spare heads for new drops; complete heads for drops; lock and chain for wall PIV; remove tape from heads in all areas being painted 10/3/2003 3:44:01 PM
INSP-Sprinkler Rough-in/Hydro9/30/200310/1/200310/1/2003ANR
DetailsRick Jackson
harry; Phone #: ###-#### Internet Inspection Request from: Darla Downs per Troy they will need resubmittals for the sprinkler system 10/1/2003 1:12:01 PM
INSP-Sprinkler Rough-in/Hydro8/19/20038/20/20038/20/2003AFAIL
DetailsTroy Cobbley
###-#### harry Sprinkler rough-in failed. See approved plans for locations and items. Issues included hanging insulation, sprinklers overspaced, hangers on bottom chords of trusses. The undergroud supply piping is ok to cover. The hydro test is ok 8/20/2003 10:43:21 AM