Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR03-00427
StatusFinaled
Name MOUNTAIN ALARM
Site Address 100 S 6TH ST
Project Namealm - CHINA BLUE BAR
Customer Number 
ePlanReview 
Description
The fire alarm system was existing for sprinkler monitoring, HVAC shutdown, notification in portions of the building, elevator recall and shutdown and door hold-opens. The remodel that is occurring involves the entire building, so all areas are to be checked for compliance and brought up to code.

The associated building permit (BLD 03-00830) is to remodel an existing 18,348 square foot building (5,565 square foot basement, 8,006 square foot first floor, 4,777 square foot second floor) for a new bar. Existing historic construction is regulated by the 1994 Uniform Code for Building Conservation (UCBC). New construction shall comply with the 2000 International Building Code (IBC). All restaurant and kitchen uses are being abandoned. Work is to include a new structural moment frame, a new stairway from the basement to the first floor (stairway enclosed in a shaft), two new stairways from the second floor to the first floor, floor modification on the first and second floors, a restroom accessible to the disabled, and interior nonbearing walls all per appproved drawings, engineering, and plan review report on file. The fire sprinkler system shall comply with NFPA 13-1999 as regulated by the Fire Department. The building is fire sprinklered for story increase and because the fire area exceeds 5,000 square feet and the occupant load exceeds 300. **CJW**
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection2/19/20042/19/20042/19/2004PPASS
DetailsRick Jackson
final okay
INSP-Sprinkler Rough-in/Hydro2/19/20042/19/20042/19/2004PPASS
DetailsRick Jackson
Final inspection for China Blue; Phone #: ###-#### Internet Inspection Request from: Robert Bailey
INSP-Final Inspection1/7/20041/9/20041/9/2004PFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Robert Bailey need updated maps and record of completion 1/9/2004 4:10:13 PM
INSP-Final Inspection1/6/20041/7/20041/7/2004ANR
DetailsRick Jackson
Aaron; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes talked to Robert and he wilol reschedule for 1/9/04 1/7/2004 3:28:32 PM
INSP-Final Inspection10/8/200310/9/200310/9/2003PFAIL
DetailsRick Jackson
Phone #: ###-#### Internet Inspection Request from: Robert Bailey NAC circuits aren't wired as shown on plans; need map with initiating devices; damper #2 detector dirty; NFPA 72 record of completion; 10/9/2003 4:35:02 PM
INSP-Final Inspection8/7/20038/6/20038/7/2003PPART
DetailsRick Jackson
performed inspection from 5-8:30 pm; NAC in basement not sync'd; horn in VIP not temporal; need to verify batteries and voltage drops