Permit Information
Permit NumberFIR03-00453
StatusFinaled
Name SENTRY SECURITY SYSTEMS
Site Address 1130 N ALLUMBAUGH ST
Project Namealm - VALLEY VIEW RETIREMENT
Customer Number 
ePlanReview 
Description
Replace three (3) existing fire alarm systems with one addressable system for an existing building. Three (3) separate occupancies (I1, I2, R2) which are located in the building will be evacuated by occupancy. The I2 will be private mode (chimes). There will be door hold-opens, elevator recall, HVAC shutdown and notification appliances.

There is no associated building permit.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
FIR-Aging Inspection7/8/20057/8/20057/8/2005 PASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection7/8/20057/8/20057/8/2005PPASS
DetailsTroy Cobbley
Permit finaled
INSP-Final Inspection10/7/200410/7/200410/7/2004PPASS
DetailsTroy Cobbley
Fire alarm system finaled
INSP-Alarm Testing8/30/20048/30/20048/30/2004PPART
DetailsTroy Cobbley
Provide connection to the hood. Suppression system still needs installed and provide NFPA 72 forms at final 8/30/2004 4:33:48 PM
INSP-Final Inspection8/25/20048/26/20048/26/2004PFAIL
DetailsTroy Cobbley
hvac unit at point 74 did not shutdown. Could not get unit at point 75 to start. Kitchen door does not latch. Flow switch at point 489 did not operate within 90 seconds. Still need to connect hood (point reports), the remaining duct smoke detectors and sprinkler risers and all of the items listed above that didn't work the first time 8/26/2004 3:45:56 PM
INSP-Final Inspection8/19/20048/19/20048/19/2004PPART
DetailsTroy Cobbley
Still need to test sprinkler risers, door closures, duct detectors and hood system 8/19/2004 4:24:18 PM
INSP-Final Inspection8/16/20048/17/20048/17/2004APART
DetailsTroy Cobbley
All of the notification devices in the central area (retirement) were tested. Spot smoke detectors in the central (retirement) area were tested. Second floor west central corridor smokes are mislabeled as first floor. 8/17/2004 4:01:41 PM
INSP-Final Inspection7/8/20047/8/20047/8/2004PPART
DetailsTroy Cobbley
Center retirement area needs inspection. Sprinkler system for the I-1 area and all elevators need tested. 7/9/2004 8:28:10 AM
INSP-Final Inspection7/7/20047/7/20047/7/2004PPART
DetailsTroy Cobbley
Inspection was for the second floor of the I-2 area. See city approved plans for locations and deficencies 7/7/2004 3:53:15 PM
INSP-Final Inspection7/1/20047/1/20047/1/2004PPART
DetailsTroy Cobbley
Tested I-2 section, first floor. See approved plans for specific location and correction. 7/1/2004 4:16:36 PM
INSP-Final Inspection6/15/20046/15/20046/15/2004PPART
DetailsTroy Cobbley
Inspection was for the assisted living area on the southwest corner of the building. All items tested except for the sprinkler flow alarms and the PIV. Some items need corrected. See city approved plans for specific items. 6/15/2004 4:08:11 PM
FIR-Aging Inspection12/17/200312/17/200312/17/2003 NR
DetailsTroy Cobbley
According to phil the work is in progress 12/17/2003 2:08:37 PM