INSP-Final Inspection | 11/24/2003 | 11/25/2003 | 11/25/2003 | P | PASS |
Troy Cobbley
|
|
|
fire life safety, fire sprinkler and fire alarm finaled 11/25/2003 3:16:28 PM
|
INSP-Final Inspection | 11/25/2003 | 11/25/2003 | 11/25/2003 | P | PASS |
Troy Cobbley
|
|
|
|
INSP-Conference | 11/4/2003 | 11/4/2003 | 11/4/2003 | P | DONE |
Troy Cobbley
|
|
|
I issued a citation to Robert Ahten with Protex for the performance of fire alarm work without a permit. Specifically the connection of an FM200 system into the existing fire alarm system.
|
INSP-Final Inspection | 10/21/2003 | 10/22/2003 | 10/22/2003 | A | PART |
Troy Cobbley
|
|
|
A temporary occupancy was given with Sam Rogers permission until the fire alarm interface with the FM200 releaseing panel has been submitted and approved. Also the egress doors with the door magnets need to be tested when installation is complete 10/22/2003 4:52:12 PM
|
INSP-Final Inspection | 10/16/2003 | 10/17/2003 | 10/17/2003 | A | FAIL |
Troy Cobbley
|
|
|
No inspection done due to work not matching plans and work done without a permit. A new FM200 suppression system has been connected to the existing fire alarm system. This work is not shown on the approved fire alarm system. Lea Electric admitted to installing the wiring between the zoned panel and the releasing panel but no contractor will admitt to who did the interconnection. I spoke to Dave Miller. A pre-citation lette will be issued and if appropriate a citation will be issued. 10/17/2003 11:23:02 AM
|