INSP-Final Inspection | 2/2/2010 | 2/2/2010 | 2/9/2010 | P | PASS |
Forrest France
|
|
|
Permit finaled, okay per subsequent work.
|
INSP-Final Inspection | 11/10/2003 | 11/12/2003 | 11/12/2003 | P | FAIL |
Rick Jackson
|
|
|
Please note school is in session until 3:30; Phone #: ###-#### Internet Inspection Request from: Terry Owsley need approved drawings; need map updated and zone 4 identified with new smokes added; tested the six smokes for door holders and okay; the plan review notes indicated duct detectors but they were not part of this project 11/12/2003 4:07:41 PM
|
INSP-Sprinkler Rough-in/Hydro | 11/10/2003 | 11/12/2003 | 11/10/2003 | P | CANC |
Rick Jackson
|
|
|
Please note that school is in session until 3:30. Have a great day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Conference | 10/14/2003 | 10/14/2003 | 10/14/2003 | P | PART |
Rick Jackson
|
|
|
stopped by the school and there are boxes with wire at locations where smoke detectors would be installed for release of new doors at serving line 10/14/2003 2:59:38 PM
|