Permit NumberFIR03-00474
StatusFinaled
Name COMMERCIAL FIRE PROTECTION
Site Address 8172 W OVERLAND RD
Project NameSPR UG Venture Development Grp
Customer Number 
ePlanReview 
Description
Venture Development Group Retail Shell Building - To install approximately 240'-0 of 6" C-900 class 50 underground fire service main from the property line in Overland Rd., North, routing along the East side of the structure, to the North East corner of the proposed 18,154-ft/2, one story type VB, fully fire sprinklered retail shell building. Separate plans and permits required for the overhead system in the building. Fire sprinklers are used for area increase. The fire sprinkler underground work shall comply with NFPA 13-1999, NFPA 24-1995 and the IFC-2000, attached review comment and conditions list, all as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-000706.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Supply line flush12/2/200312/2/200312/2/2003PPASS
DetailsRick Jackson
UG flush only okay 12/2/2003 3:36:44 PM
INSP-Sprinkler Rough-in11/10/200311/12/200311/12/2003APART
DetailsRick Jackson
Bruce; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes okay to cover outside canopy - plans show 155 heads but 200 installed; dry pendants not installed 11/12/2003 8:57:44 AM
INSP-Sprinkler Rough-in/Hydro10/6/200310/6/200310/6/2003PPART
DetailsRick Jackson
BRUCE; Phone #: ###-#### Internet Inspection Request from: Annette Moore UG hydro okay 10/6/2003 4:05:39 PM
INSP-Sprinkler Rough-in8/22/20038/25/20038/25/2003APART
DetailsTroy Cobbley
Underground sprinkler piping is OK to cover 8/25/2003 10:47:09 AM