INSP-Final Inspection | 11/17/2003 | 11/18/2003 | 11/18/2003 | A | PASS |
Troy Cobbley
|
|
|
Please notify Warner for time of inspection.; Phone #: ###-#### Internet Inspection Request from: Teresa Costello
|
INSP-Final Inspection | 11/14/2003 | 11/17/2003 | 11/17/2003 | A | FAIL |
Troy Cobbley
|
|
|
contractor did not have keys to riser room 11/17/2003 9:59:18 AM
|
INSP-Final Inspection | 11/10/2003 | 11/14/2003 | 11/14/2003 | P | FAIL |
Troy Cobbley
|
|
|
Duct smoke detectors in blockbuster video need to be retested since the wrong address came in at the monitoring service. All other items are ok. 11/14/2003 2:07:11 PM
|
INSP-Final Inspection | 10/17/2003 | 10/22/2003 | 10/22/2003 | P | FAIL |
Troy Cobbley
|
|
|
Provide tamper switch on the anti-freeze system control vavle, provide correct orfice on the sprinkler inspectors test vavles and test flow switches, test duct detectors in 1405,1447 since units would not turn on, test duct detector in 1421 again since central station did not have an address listed, test all remaining duct detectors beyond 1513. Phone lines, batteries, tamper switches and duct detectors up to 1513 that are not listed above are ok. 10/22/2003 2:51:03 PM
|