INSP-Final Inspection | 11/17/2003 | 11/17/2003 | 11/17/2003 | P | PASS |
Troy Cobbley
|
|
|
PAT CELL PHONE; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
INSP-Final Inspection | 11/14/2003 | 11/14/2003 | 11/14/2003 | P | FAIL |
Troy Cobbley
|
|
|
verify all signals, test phone lines, repair duct smoke detector, provide remote alarm led for duct detector in corridor 11/14/2003 3:30:13 PM
|
INSP-Final Inspection | 10/2/2003 | 10/2/2003 | 10/2/2003 | P | PART |
Rick Jackson
|
|
|
pat ###-#### will need map with zones at annunciator; will complete testing after the rest of the RTU's are installed; tested RTU's in toy store and everton only; sprinkler system tested for flow and tampers 10/2/2003 5:08:57 PM
|
INSP-Conference | 9/26/2003 | 9/26/2003 | 9/26/2003 | P | DONE |
Troy Cobbley
|
|
|
I stopped by the project to verify if work had been done without permits. Work had indeed been performed without permits. According to Patrick, who was the installer of the fire alarm system, he pulled off the job the previous week. I talked to Barbara at the permit desk and had her double the permit fees as per policy. The contractor picked up the drawings shortly after. Dave Miller has instrucked me to cite the offending party.
|