Permit Information
Permit NumberFIR03-00586
StatusFinaled
Name AIC SOLUTIONS INC
Site Address 6565 W EMERALD ST
Project Namealm - Selah Medical Center
Customer Number 
ePlanReview 
Description
To add additional tamper switch monitoring to the sprinkler system. The existing fire alarm system is a required sprinkler monitoring that includes door release and partial area coverage.

12/14/2004 - Revised scope, the original fire alarm control panel was replaced with a Firelite MS-5012. An ESL 505 module will be used for connecting the ESL 429CT smoke detectors (compatibility listing is included in the packet). The battery calculations indicate a minimum battery size of 9.73 a-h, the 12V FACP will hold 7 a-h batteries. The installed battery size is not defined and will be field verified by the PDS Fire Inspector. The revised fire alarm matrix indicates that on alarm, the FACP will "unlock exits", but no output from the panel is shown to be connected to the exits for release. The PDS Fire Inspector shall field verify the FACP releases the exits upon alarm.

1/19/2005 - This plan modification defines the new FACP (Fire Lite MS 5012) that has the same functionality as the previous panel and is compatible with the initiating devices already installed except that it has "latching" supervisory signals.

NFPA 72 (2002) specifically addresses both non-latching and latching supervisory signals (4.4.3.2.3 and 4.4.3.2.4). Per NFPA 72, 6.8.5.7.5, "Where approved by the AHJ, supervisory signals that latch in the off-normal state and require manual reset of the system to restore them to normal shall be permitted." Dave Miller, Boise City Fire Marshall, has agreed to this panel being installed.

This plan modification also addresses the following:

" Two 12v, 7 a-h batteries will be installed in the 12v system to meet the calculated a-h capacity.
" West side of main lobby, seven (7) smoke detectors that were originally installed for fire/smoke door release are being removed, the two (2) roll-up fire/smoke doors are deactivated in the OPEN position and the door hold-open on the northwest hall will also be deactivated.

The PDS Fire Inspector shall field verify battery monitoring capabilities, removal of smoke detectors and the position of the fire/smoke doors.

The associated building permit (BLD 03-01575) is to construct 3 offices and a conference room within an existing 12,213 square foot medical office building. Two existing restrooms are also being altered to be accessible to the disabled. Work is to include interior nonbearing walls, interior doors, interior windows, and suspended ceilings all per the approved drawings and plan review conditions on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. **CJW** (SELAH MEDICAL CENTER) This building is fire sprinklered to allow non-fire-resistance rated corridors.

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/31/200510/31/200510/31/2005PPASS
DetailsTroy Cobbley
Fire alarm permit finaled
FIR-Aging Inspection10/24/200510/24/200510/31/2005 PASS
DetailsTroy Cobbley
permit finaled
FIR-Aging Inspection7/28/20057/28/20058/1/2005 NR
DetailsTroy Cobbley
Per Brian with AIC he will contact the owner again to provide the knox key box.
INSP-Conference5/26/20055/26/20055/26/2005PDONE
DetailsTroy Cobbley
I spoke to Brian with AIC Solutions and let him know that all that is needed is the Knox Key box.
FIR-Aging Inspection4/6/20054/6/20054/6/2005PPEND
DetailsForrest France
I called Brian with AIC solutions, ###-####, and left a message on his voice mail requesting status of the fire alarm installation
INSP-Final Inspection2/4/20052/4/20052/4/2005PFAIL
DetailsTroy Cobbley
Provide knox key box. The tamper switches for the backflow preventor did not annunciate separately from the other tamper switch as required by IFC 903.4.1. Need record of completion nfpa form at final. 2/4/2005 3:16:57 PM
INSP-Final Inspection12/16/200412/17/200412/17/2004PFAIL
DetailsTroy Cobbley
Battery calcs, flow switch, battery supervision and smoke detectors on the east side of building (5 total) operate correctly. Inspection stopped after finding the items listed. The monitoring company is not getting all of the signals sent such as Phone line 1 and low battery. Smoke detectors on the west half of the building annunciate locally but do not report to the panel. The tamper switches supervisory signal is latching and is not supposed to per nfpa 72 4.4.3.2.4. Per the manufacturer the panel can't be reprogrammed. 12/17/2004 1:56:55 PM
INSP-Final Inspection11/16/200411/17/200411/17/2004PCANC
DetailsTroy Cobbley
A new fire alarm panel has been installed. Contractor needs to resubmit plans for plan modifications 11/17/2004 3:45:38 PM
INSP-Final Inspection10/25/200410/25/200410/25/2004PFAIL
DetailsTroy Cobbley
Inspection was stopped due to so many items being incorrect. Phone lines are not being supervised. Smoke detector installed is not the one submitted. Supervisory signal latches. No map of initiating devices. Need zone description at annunciator. No one to test the new tamper switches. Strobe does not work.
INSP-Conference3/9/20043/9/20043/9/2004ADONE
DetailsTroy Cobbley
Odie with Steed Construction called wanting to know the status of the fire alarm drawings. I quoted the history.
INSP-Conference3/3/20043/3/20043/3/2004ADONE
DetailsTroy Cobbley
At Mary's request I stopped at this project to verify if smoke detectors are installed and if possible the reason they are installed. I found smoke detectors installed on the left hand side of the lobby at three fire doors and what appears to be area coverage through out the office area to the right of the lobby. The smoke detectors at the fire doors are mounted on the walls on the lobby side and appear to exceed 12" down from the ceiling