INSP-Final Inspection | 7/26/2004 | 7/26/2004 | 7/26/2004 | P | PASS |
Troy Cobbley
|
|
|
Fire sprinklers finaled
|
INSP-Sprinkler Rough-in/Hydro | 7/22/2004 | 7/22/2004 | 7/22/2004 | P | PART |
Troy Cobbley
|
|
|
Forward flush of the backflow preventer and the additional head in the closet are ok. Still need alarm connections and hanger from previous correction notice to be done. 7/22/2004 1:58:54 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/20/2004 | 7/21/2004 | 7/21/2004 | A | PASS |
Troy Cobbley
|
|
|
Hydro test for the wet system passed. Provide forward flush of the backflow preventor per review note #9. Provide signage. Provide alarm interconnections between FACP and new dry pipe riser. Provide head in closet and provide hanger per previous correction notice. 7/21/2004 2:25:31 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/16/2004 | 7/16/2004 | 7/16/2004 | P | PASS |
Troy Cobbley
|
|
|
24 hour test of the existing dry system is ok 7/16/2004 4:06:06 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/14/2004 | 7/15/2004 | 7/15/2004 | A | PART |
Troy Cobbley
|
|
|
Hydro tests for both dry systems are ok. 24 hour test on the second dry system started at 12:45 at 67psi 7/15/2004 12:44:05 PM
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2004 | 7/13/2004 | 7/13/2004 | A | PART |
Troy Cobbley
|
|
|
24 hour air test on the new dry system is ok. Rough-in inspection on the remaining first floor offices is ok except for one additional head and one hanger that need to be added. See plans for location. 7/13/2004 9:45:57 AM
|
INSP-Sprinkler Rough-in/Hydro | 7/12/2004 | 7/13/2004 | 7/13/2004 | A | PART |
Troy Cobbley
|
|
|
24 hour air test on the new dry system is ok. Rough-in inspection on the remaining first floor offices is ok except for one additional head and one hanger that need to be added. See plans for location. 7/13/2004 9:45:57 AM
|
INSP-Sprinkler Rough-in | 7/9/2004 | 7/12/2004 | 7/12/2004 | A | PART |
Troy Cobbley
|
|
|
24 hour air test started at 9:00am with 47 1/2 psi 7/12/2004 9:41:27 AM
|
INSP-Sprinkler Rough-in | 6/18/2004 | 6/21/2004 | 6/21/2004 | A | PART |
Troy Cobbley
|
|
|
Sprinkler rough-in for first and second floor east side offices OK. See approved plans for specific locations. 6/21/2004 10:09:27 AM
|
INSP-Sprinkler Rough-in | 6/1/2004 | 6/2/2004 | 6/2/2004 | A | PART |
Rick Jackson
|
|
|
Contact: Chris; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley See approved plans for areas inspected - highlighted areas only 6/2/2004 11:29:20 AM
|
FIR-Aging Inspection | 3/30/2004 | 3/30/2004 | 3/30/2004 | | NR |
Troy Cobbley
|
|
|
Per Randy with Debest Fire work is in progress 3/30/2004 3:35:26 PM
|