Permit Information
Permit NumberFIR03-00780
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 6126 W STATE ST
Project NameSPR SEL EQUITY REAL ESTATE
Customer Number 
ePlanReview 
Description
Sel Equity Real Estate Office Building * To install a wet and dry fire sprinkler system for a new 7,830 square foot, two story, wood framed office building on the east side of an existing two story 5,868-ft/2, two story, Type VB (non sprinklered) office building. The new building first floor 4,760-ft/2, second floor 3,070-ft/2, for a total 7,830-ft/2. The new building will be separated from the existing building by a two-hour fire resistive fire wall. This new building will be fully fire sprinklered. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-01695.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Sprinkler Rough-in4/12/20044/13/20044/13/2004APASS
DetailsTroy Cobbley
fire sprinklers finaled 4/13/2004 8:23:25 AM
INSP-Final Inspection4/12/20044/12/20044/12/2004PFAIL
DetailsTroy Cobbley
forward flush failed through the 2" drain. Provide heat for the riser room 4/12/2004 2:32:20 PM
INSP-Sprinkler Rough-in/Hydro4/5/20044/6/20044/6/2004APASS
DetailsTroy Cobbley
24 hour air test passed 10/15/2003 11:24:50 PM
INSP-Sprinkler Rough-in/Hydro4/5/20044/5/20044/5/2004PPASS
DetailsTroy Cobbley
dry system hydro test passed. 24 hour air test started at 2:45 with 50psi 4/6/2004 8:17:47 AM
INSP-Supply line flush3/31/20043/31/20043/31/2004PPASS
DetailsTroy Cobbley
above ground wet system and underground hydro test ok. Flush of the underground supply line flush is ok 3/31/2004 4:13:12 PM 3/31/2004 4:13:36 PM
INSP-Sprinkler Rough-in/Hydro2/11/20042/11/20042/11/2004PFAIL
DetailsTroy Cobbley
provide hangers on the 1 1/4" supplies and the sprinkler pendant in the mechanical room is still overspaced 2/11/2004 3:40:51 PM
INSP-Sprinkler Rough-in/Hydro2/6/20042/9/20042/9/2004PFAIL
DetailsTroy Cobbley
Inspection was for the rough-in and cover of the first floor. 1 1/4" tie in's are not done, pendant head overspace in mechanical room, pendant head overspaced understairs in connecting corridor and piping not complete in rooms as marked on approved plans. Outside canopies are ok to cover 2/9/2004 4:21:17 PM
INSP-Sprinkler Rough-in/Hydro2/5/20042/6/20042/6/2004PCANC
DetailsTroy Cobbley
Scheduled by a contractor via Hello! on 2/5/2004 at 3:19:45 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Feb 6 2004 9:22AM.
INSP-Sprinkler Rough-in/Hydro1/29/20041/29/20041/29/2004APART
DetailsTroy Cobbley
sprinkler piping on the second floor between the two large beams is ok to cover. The north and south canopies are ok to cover except for the end of each branchlines. These need re-inspected due to blocked upright sprinkler coverage
INSP-Sprinkler Rough-in/Hydro1/27/20041/28/20041/28/2004ACANC
DetailsTroy Cobbley
areas needing inspection are not ready 1/27/2004 3:17:22 PM
INSP-Sprinkler Rough-in/Hydro1/22/20041/23/20041/23/2004AFAIL
DetailsTroy Cobbley
hangers must go to top chord. Provide head in mech. room. Provide insulation in the void in the east canopy. tent plastic piping. Inspection was for the central part of the second floor (area between the beams). 1/23/2004 2:04:26 PM