Permit Information
Permit NumberFIR03-00806
StatusFinaled
Name DE BEST FIRE PROTECTION
Site Address 707 N ARMSTRONG PL
Project NameSPR ID Public Health Dist #4
Customer Number 
ePlanReview 
Description
Central District Health Department (Addition) * To separate and breakup an existing dry pipe system and install a new dry pipe system for the new additions unheated 3,500-ft/2 attic. Also to extend an existing wet system into the new 3,500-ft/2 one story office addition. This addition is located on the north side of the existing 39,500-ft/2, one story Central District Health office building. The sprinklers are used for allowable area increase. The fire sprinkler system work shall comply with IFC 2000, attached review comment and conditions list, as regulated by the Fire Chief. These notes, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-01797.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/29/20046/29/20046/29/2004APASS
DetailsTroy Cobbley
Fire sprinkler finaled
INSP-Sprinkler Rough-in3/12/20043/15/20043/15/2004APASS
DetailsTroy Cobbley
Main rough-in ok 3/15/2004 10:08:31 AM
INSP-Sprinkler Rough-in/Hydro3/11/20043/12/20043/12/2004APASS
DetailsTroy Cobbley
hydro test on the dry pipe riser is OK 3/12/2004 11:20:23 AM
INSP-Sprinkler Rough-in/Hydro3/10/20043/11/20043/11/2004PPART
DetailsTroy Cobbley
24 hour air test is ok 3/11/2004 4:30:25 PM
INSP-Sprinkler Rough-in/Hydro3/9/20043/10/20043/10/2004PPART
DetailsTroy Cobbley
Inspection was for the start of the 24 hour air test. Piping in the attic is at 49psi and the riser is at 46psi 3/10/2004 3:04:56 PM
INSP-Sprinkler Rough-in/Hydro3/8/20043/9/20043/9/2004PPART
DetailsTroy Cobbley
wet and dry system hydro test are ok 3/9/2004 4:06:43 PM
INSP-Final Inspection2/12/20042/12/20042/12/2004APART
DetailsTroy Cobbley
Temporary occupancy was given until all of the fire mains are upgraded per plans submitted to boise city and the fire alarm system is completed
INSP-Sprinkler Rough-in/Hydro1/27/20041/28/20041/28/2004APART
DetailsRick Jackson
Scheduled by a contractor via Hello! on 1/27/2004 at 1:33:26 PM. Contact: ###-####. okay to cover wet system in office area - the 2.5 inch is not completed at the tie-in to the exsisting main; the dry system is installed in the attic area but the 4 inch main is not completed where it passes through the roof to tie it into the new riser (see plans) 1/28/2004 10:46:40 AM