INSP-Final Inspection | 6/25/2004 | 6/25/2004 | 6/25/2004 | P | PASS |
Rick Jackson
|
|
|
|
INSP-Alarm Testing | 6/23/2004 | 6/24/2004 | 6/24/2004 | P | FAIL |
Rick Jackson
|
|
|
LINDA; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Duct detectors not shutting off HVAC units and the ARM's aren't showing activation with the LED 6/24/2004 4:04:36 PM
|
INSP-Final Inspection | 6/3/2004 | 6/8/2004 | 6/8/2004 | P | FAIL |
Rick Jackson
|
|
|
Terry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Sprinkler bell not working; address wrong for dispatching from monitoring company; duct detectors relay not latching 6/8/2004 3:52:12 PM
|
INSP-Final Inspection | 4/14/2004 | 4/15/2004 | 4/15/2004 | A | FAIL |
Rick Jackson
|
|
|
please call teri before going out ; Phone #: ###-#### Internet Inspection Request from: Darla Downs Resubmittals needed for 6 new tampers on the anti-freeze loop and deletion of the knox box tamper; sign on riser door; address was wrong the monitoring account 4/15/2004 1:52:39 PM
|
INSP-Final Inspection | 4/8/2004 | 4/9/2004 | 4/9/2004 | A | FAIL |
Rick Jackson
|
|
|
Terry; Phone #: ###-#### please call first for access. Internet Inspection Request from: Aimee Hughes Extension given on temp occupancy for Mazzeh as the new alarm system isn't completed; tested the hood extinguishing system and it sent alarm signal to new panel; all of the water flows/tampers not connected to the new panel 4/9/2004 1:41:09 PM
|