Permit NumberFIR04-00010
StatusFinaled
Name PEAK ALARM
Site Address 1772 W STATE
Project Namealm - ALBERTSONS MARKETPLACE
Customer Number 
ePlanReview 
Description
To install a new required sprinkler monitoring fire alarm system in an existing building.
2/17/2004 - To replace and relocate an existing sprinkler monitoring fire alarm system. The new system will include sprinkler monitoring, HVAC shutdown and monitoring of a cooking hood. There are six (6) conventional smoke detectors located in the tenant spaces that will be removed. A Radionics FACP with smoke detector coverage will also be removed.

The associated building permit (BLD 03-02729) is to remodel a 1,365 sq. ft. existing sandwich shop for new restaurant tenant per approved plans. Work to include, installation of a new one-hour hood system and grease duct. Grease duct to be wrapped with fire master duct wrap. Miscellaneous related interior finishes. This building is fully fire sprinklered any alterations or modifications to the sprinkler system shall be per NFPA #13 as regulated by the fire department. (pc#707-03) rmh (MAZZEH RESTAURANT)(ALBERTSONS MARKETPLACE)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/25/20046/25/20046/25/2004PPASS
DetailsRick Jackson
INSP-Alarm Testing6/23/20046/24/20046/24/2004PFAIL
DetailsRick Jackson
LINDA; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Duct detectors not shutting off HVAC units and the ARM's aren't showing activation with the LED 6/24/2004 4:04:36 PM
INSP-Final Inspection6/3/20046/8/20046/8/2004PFAIL
DetailsRick Jackson
Terry; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes Sprinkler bell not working; address wrong for dispatching from monitoring company; duct detectors relay not latching 6/8/2004 3:52:12 PM
INSP-Final Inspection4/14/20044/15/20044/15/2004AFAIL
DetailsRick Jackson
please call teri before going out ; Phone #: ###-#### Internet Inspection Request from: Darla Downs Resubmittals needed for 6 new tampers on the anti-freeze loop and deletion of the knox box tamper; sign on riser door; address was wrong the monitoring account 4/15/2004 1:52:39 PM
INSP-Final Inspection4/8/20044/9/20044/9/2004AFAIL
DetailsRick Jackson
Terry; Phone #: ###-#### please call first for access. Internet Inspection Request from: Aimee Hughes Extension given on temp occupancy for Mazzeh as the new alarm system isn't completed; tested the hood extinguishing system and it sent alarm signal to new panel; all of the water flows/tampers not connected to the new panel 4/9/2004 1:41:09 PM