Permit Information
Permit NumberFIR04-00011
StatusFinaled
Name PROTEX
Site Address 2252 S SUMPTER WAY
Project Namealm -Pepperhills/elem School
Customer Number 
ePlanReview 
Description
To provide a required manual fire alarm system (per IFC 907.4, manual fire alarm boxes are not required if the building if equipped with an approved automatic sprinkler system and the notification appliances will activate on water flow) that includes sprinkler monitoring, HVAC shutdown, supplemental coverage in specified areas and notification throughout.

4/28/2004 - The fire alarm system will include door release.

The associated building permit (BLD 03-00781) is to construct a 61,000 sq. ft., one story, Type VA-1hr, fully fire sprinklered elementary school in accordance with the approved plans and attachments, CUP02-00135. Other work includes all site improvements, grading, paving and landscaping. All construction must be done in accordance with the City flood plain ordinance. Flood plain certificates are to be submitted prior to calling for final inspection. Fire sprinklers used for area. Pepperhills Elementary School *

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection7/13/20047/13/20047/13/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection7/13/20047/13/20047/13/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection7/13/20047/13/20047/13/2004APASS
DetailsTroy Cobbley
Fire alarm finaled
INSP-Final Inspection6/29/20046/29/20046/29/2004PPART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers permission. Fire alarm plan modifications have been resubmitted to the city of boise. If school is to be occupied prior to final sign off a fire watch will be required.
INSP-Final Inspection6/28/20046/28/20046/28/2004PFAIL
DetailsTroy Cobbley
Need fire alarm resubmittals approved. All other items are OK.
INSP-Final Inspection6/24/20046/25/20046/25/2004AFAIL
DetailsRick Jackson
Rick This is Grants cell. Have a Great Day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Need cages on strobes in auditorium; provide as-builts for NAC's to owner 6/25/2004 4:39:58 PM
INSP-Final Inspection6/23/20046/24/20046/24/2004PFAIL
DetailsTroy Cobbley
Resubmit plans showing additional devices. Backflow preventors to annunciate separately. Provide in-duct detectors instead of duct detectors at the fire/smoke dampers. Smoke detectors are over spaced in hall 165, library and outside of the admin. office. Provide signage on fire sprinkler riser door. No notification devices have been verified for spacing or function. 6/24/2004 3:08:35 PM
INSP-Final Inspection6/22/20046/23/20046/23/2004PCANC
DetailsTroy Cobbley
This is Robs cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley