Permit Information
Permit NumberFIR04-00021
StatusFinaled
Name PROTEX
Site Address 707 N ARMSTRONG PL
Project NamealmIdaho Public Health Dist #4
Customer Number 
ePlanReview 
Description
FA Scope is undefined at this time. Plans show three (3) duct detectors in the new space.
2/9/2004 - To extend the existing required fire alarm system into the new space with notification throughout and HVAC shutdown for three (3) duct detectors. The existing system includes HVAC shutdown, sprinkler monitoring, partial area detection and notification. Four (4) pull stations and two (2) smoke detectors were added in the existing area. (Exterior exits and FACP, control panels for the fire alarm system).

4/30/2004 - Plan Modification: A new NAC panel is being added to accommodate the voltage drop issue from the FA inspection, sprinkler monitoring points for a new dry system, PIV and backflow preventer valves.

5/25/2004 - Plan Modification: Architectural change. A single office has been divided in to two. A new NAC appliance is added to accommodate visual and audible coverage.

The associated building permit (BLD 03-01797) is to construct a 3500 square foot, one story office addition on the north side of the existing 39,500 square foot, one story Central District Health office building and related site improvements. The sprinklers are used for allowable area increase. This building is now at the maximum allowable area under the 2000 IBC. All construction per the approved plans and attached comment list. DRH03-00123/CUP03-00064/PC#427-03/JCM Central District Health Department (Addition) *
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/28/20046/29/20046/29/2004APASS
DetailsTroy Cobbley
Fire alarm finaled 6/29/2004 9:59:06 AM
INSP-Final Inspection6/15/20046/18/20046/18/2004AFAIL
DetailsTroy Cobbley
Provide a/v coverage in the corridor per the last correction notice. Change the 30cd strobe to 15cd in Rob's office. Provide signage on doors to facp and sprinkler riser per review note #23. Test low air signal on dry pipe riser 6/18/2004 9:33:41 AM
INSP-Final Inspection6/9/20046/14/20046/14/2004ACANC
DetailsTroy Cobbley
Inspection was cancelled by Rob with Protex 6/14/2004 8:33:34 AM
INSP-Final Inspection3/12/20043/18/20043/18/2004AFAIL
DetailsTroy Cobbley
Resubmit fire alarm plans that include all devices including the second dry pipe valve, backflow preventor and the additional three duct smoke detectors. End of line voltage on the notification circuits exceeds 21.6 volts(nfpa 72, 7.3.2.3). Provide verification/explanation on resubmittals on why remaining hvac units do not have automatic shutdown per IMC. Office and corridor areas that open into the new addition must be brought up to code compliance. Only the items listed above have been inspected and addressed. All other items to be verified when resubmitted plans have been issued 3/18/2004 9:41:04 AM
INSP-Final Inspection2/12/20042/12/20042/12/2004APART
DetailsTroy Cobbley
Temporary occupancy was given until all of the fire mains are upgraded per plans submitted to boise city and the fire alarm system is completed