Permit NumberFIR04-00040
StatusFinaled
Name PROTEX
Site Address 12601 W EXPLORER DR Unit: 100
Project Namealm - BRIGHTON PLAZA
Customer Number 
ePlanReview 
Description
To add one (1) in-duct smoke detector for fire/smoke damper control (relocated damper) and thirteen (13) duct smoke detectors and two smoke detector for door release to an existing required sprinkler monitoring fire alarm system that includes elevator recall/shutdown, HVAC shutdown and door release and fire/smoke damper control.

The associated building permit (BLD 03-02993) is to create a 13,761 square foot tenant space located on the 1st floor of an existing 2 story building. This tenant space will have training rooms, a conference room, a waiting room, a lunch room, offices, and office cubicles. A portion of the existing 1-hr corridor on the 1st floor is being incorporated into this tenant space. "Training Room 117" and "Conference Room 115" are both assembly occupancies. Occupant load signage shall be posted at 52 and 55, respectively. Work is to include interior nonbearing walls, a shower room accessible to the disabled, alterations to the 1-hr corridor, millwork, and interior finishes all per the approved drawings and the plan review report on file. The location of fire sprinkler heads shall comply with NFPA 13-1999 as regulated by the Fire Department. The 4,145 square foot adjacent space must receive its own Certificate of Occupancy before it is occupied. **CJW** (BOISE HUB - STATE FARM INSURANCE - STE 100) This building is fire sprinklered for increase in allowable area.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection3/24/20043/25/20043/25/2004APASS
DetailsRick Jackson
8:00
INSP-Final Inspection3/23/20043/24/20043/24/2004ADONE
DetailsRick Jackson
Scheduled by a contractor via Hello! on 3/23/2004 at 2:44:17 PM. Contact: ###-####. Per troy this was done yesterday 3/24/2004 8:02:17 AM
INSP-Final Inspection3/23/20043/23/20043/23/2004PFAIL
DetailsTroy Cobbley
Door holders did not release. Contractor did not define zones 18, 19 and 20 with the monitoring company. Signals will need to be verified on these zones. Need nfpa 72 forms.
INSP-Final Inspection3/22/20043/23/20043/23/2004PFAIL
DetailsTroy Cobbley
Unable to verify signals, missing smoke detector for door release. Verify induct smoke detector work was performed 3/23/2004 1:39:43 PM
INSP-Final Inspection3/19/20043/19/20043/19/2004PFAIL
DetailsTroy Cobbley
No devices tested. The remote alarm LED's for the duct smoke detectors did not operate 3/19/2004 4:06:17 PM