INSP-Final Inspection | 4/1/2004 | 4/2/2004 | 4/2/2004 | A | PASS |
Rick Jackson
|
|
|
this is robs cell; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
|
INSP-Final Inspection | 3/31/2004 | 4/1/2004 | 4/1/2004 | A | FAIL |
Rick Jackson
|
|
|
This is Grants cell Have a great day!; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Need approved plans 4/1/2004 12:35:09 PM
|
INSP-Final Inspection | 3/29/2004 | 3/31/2004 | 3/31/2004 | P | CANC |
Rick Jackson
|
|
|
This is for the Tanning portion.
You can contact Rob.; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Inspection cancelled from web by: Terry Owsley
|
INSP-Final Inspection | 3/5/2004 | 3/5/2004 | 3/8/2004 | P | PART |
Rick Jackson
|
|
|
Scheduled by a contractor via Hello! on 3/5/2004 at 7:30:27 AM. Contact: ###-####. Phase I okay to occupy; will need to complete alarms in the tanning area as part of Phase II 3/8/2004 9:52:51 AM
|
INSP-Final Inspection | 3/4/2004 | 3/4/2004 | 3/4/2004 | P | FAIL |
Rick Jackson
|
|
|
this is robs cell could we please schedule it for after 2:30 pm; Phone #: ###-#### Internet Inspection Request from: Terry Owsley Strobes not sync'd; need to test voltage drops and current draw on NAC's 3/4/2004 5:06:05 PM
|
INSP-Conference | 2/19/2004 | 2/19/2004 | 2/19/2004 | P | PART |
Rick Jackson
|
|
|
This is Robs Cell Phone Thanks Rick, Have a great day; Phone #: ###-#### Internet Inspection Request from: Terry Owsley met with Rob about strobe placement at pool area and it will have to be installed at plan location or hang strobe from ceiling; elevator smoke detector to comply with state inspection as the two floor elevator has open lobbies to both floors 2/19/2004 1:59:58 PM
|
INSP-Conference | 2/12/2004 | 2/12/2004 | 2/12/2004 | A | PART |
Rick Jackson
|
|
|
Site visit to check on fire alarm install - conduit being installed by ProTech; they weren't sure who was going to pull the wire 2/12/2004 10:40:18 AM
|