Permit Information
Permit NumberFIR04-00142
StatusFinaled
Name TREASURE VALLEY FIRE PROTECTION
Site Address 3562 S TK AVE
Project NameSPR IDAHO FOODBANK
Customer Number 
ePlanReview 
Description
(IDAHO FOODBANK - OFFICE ARE EXPANSION) To modify and add fire sprinklers for the expansion of an existing two story office area located within an existing warehouse building. The 1st floor office area is being expanded to 3,051-ft/2 and the 2nd floor office area, located directly above, is being expanded to 2,998-ft/2. Fire sprinkler work is related to shear walls, a folding partition and a new stairway. Storage racks are being installed under BLD03-02460. This building is fire sprinklered for building area increase and for fire area. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. This permit is attached to building permit: BLD03-02476.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/14/20046/15/20046/15/2004APASS
DetailsRick Jackson
Scheduled by a contractor via Hello! on 6/14/2004 at 12:18:25 PM. Contact: ###-####.
INSP-Conference6/10/20046/10/20046/10/2004PPART
DetailsRick Jackson
Talked to Jeff of TVFP about the EQ on the new main added and the 2nd floor mechanical room - no ceiling and uprights may be overspaced from east wall above duct work 6/10/2004 2:31:56 PM
INSP-Final Inspection4/21/20044/22/20044/22/2004PFAIL
DetailsRick Jackson
Scheduled by a contractor via Hello! on 4/21/2004 at 1:40:17 PM. Contact: ###-####. Okay to cover the office area but the new main to feed the office area requires EQ 4/22/2004 2:44:32 PM
INSP-Sprinkler Rough-in3/29/20043/29/20043/29/2004PFAIL
DetailsRick Jackson
john; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie Cold soldering on first floor hall/storage room for upright heads; overspaced at wall to storage area and exterior wall for office area at roof; need spare heads; line on first floor shifted east to keep heads 6 ft apart 3/29/2004 2:14:20 PM