Permit Information
Permit NumberFIR04-00162
StatusFinaled
Name FIRE SENTRY SYSTEMS
Site Address 3323 N LAKEHARBOR LN
Project NameSILVER LAKE APARTMENTS
Customer Number 
ePlanReview 
Description
A required manual and automatic fire alarm system is required for all group R-1 occupancies. (UFC 1007.2.9) The fire alarm system will include sprinkler monitoring.

The associated building permit (BLD 02-01157) is to construct a new 16,416 sq.ft. three story, wood framed, 18 unit apartment building. The first floor is 7,506 sq.ft. and the second floor is 7,080 sq.ft. and the third floor is 1,830 sq.ft. NOTE: This building is fire sprinklered per NFPA 13-R. All construction per the approved plans and attached comment list. PC #310-02 DRH01-00233 SS CUP01-00159 DAA (Building B)

Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection6/25/20046/25/20046/25/2004APASS
DetailsRick Jackson
INSP-Alarm Testing6/23/20046/24/20046/24/2004AFAIL
DetailsTroy Cobbley
Repair horns in rooms 201 and 104. Repair flow switch. Provide signage on door to riser and facp. 6/24/2004 2:51:33 PM
INSP-Alarm Testing6/22/20046/23/20046/23/2004PCANC
DetailsTroy Cobbley
Cancelled by contractor. 6/23/2004 4:25:51 PM
INSP-Final Inspection5/27/20045/27/20045/27/2004PFAIL
DetailsTroy Cobbley
No actual inspections were done. At the start of the fire sprinkler inspection I found that a different backflow preventor has been installed. Verification of friction loss is needed. Need NFPA 25. Provide verification that exposed cpvc sprinkler piping in the riser room is ok. Also per inspector 409 the fire sprinkler plans need to be resubmitted which has not been done yet according to the history available on the computer. Fire alarm plans need to be resubmitted due to changes in zones and notification circuitry.