Description
(Bown Crossing Market Place-Bldg C) * To install fire sprinkler protection in a new 5,550-ft/2 two story, multi-tenant, shell building. The main floor will be protected for OH-2, "M" occupancy and the second floor will be protected for Light Hazard, "B" (office). The first floor is 2,878-ft/2 and the second floor is 2,672-ft/2. This building is fully fire sprinklered for Code and allowable fire flow reduction. Separate permits, plans must be obtained and approved for each tenant space to be occupied. The fire sprinkler system work shall comply with the IFC 2000, the attached review comments/conditions, as regulated by the Fire Chief. The review comments/conditions, permit and fire "Inspection Card" are required to be on site as a condition of this work, to provide witness of compliance verification of minimum code. The underground fire service supply was installed under FIR04-00112. This permit is attached to building permit: BLD03-02191.
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection12/10/200412/10/200412/10/2004APASS
DetailsRick Jackson
Final okay 12/10/2004 9:03:13 AM
INSP-Final Inspection12/8/200412/9/200412/9/2004AFAIL
DetailsRick Jackson
Burl; Phone #: ###-#### Internet Inspection Request from: Jan Rice Need approved plans; horn instead of horn/stobe; duct detectors to be supervisory per plans 12/9/2004 10:33:55 AM
INSP-Final Inspection12/8/200412/8/200412/8/2004PFAIL
DetailsRick Jackson
Burl; Phone #: ###-#### Internet Inspection Request from: Jan Rice Need maps; zones defined; approved plans; account not active; sprinkler flow switch on bottom of pipe 12/8/2004 5:02:43 PM
INSP-Sprinkler Rough-in10/22/200410/22/200410/22/2004APART
DetailsRick Jackson
EQ, sidewalls and hangers on 2nd floor okay 10/22/2004 10:53:37 AM
INSP-Sprinkler Rough-in/Hydro10/20/200410/20/200410/20/2004PFAIL
DetailsRick Jackson
mike; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Sidewalls need to be 4-6 inches below ceiling; straps on second floor; EQ riser; hydro okay FDC will need hydro 10/20/2004 4:05:50 PM
FIR-Aging Inspection6/24/20046/24/20046/24/2004 PASS
DetailsRick Jackson
Building still under construction 6/24/2004 7:11:40 AM