INSP-Sprinkler Rough-in/Hydro | 6/30/2004 | 7/1/2004 | 7/1/2004 | A | PASS |
Rick Jackson
|
|
|
Contact: Mike Leiser - This is a hydro test, would like done around 11 am, please call Mike to confirm 7-1-04; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Per Bill Alexander the new copper line under the bar canopy will not require sprinkler plan mofications; the semi-portable table canopies will not require sprinklers 7/1/2004 4:06:29 PM
|
INSP-Sprinkler Rough-in | 6/14/2004 | 6/15/2004 | 6/15/2004 | A | PART |
Rick Jackson
|
|
|
Contact: Charles -- R-In for Antifreeze loop; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Met with Charles about getting submittals for sprinklers under the new bar located on the terrace; the new bar was not shown on the resubmittals and is in the calc'd area 6/15/2004 10:31:35 AM
|
INSP-Sprinkler Rough-in | 6/2/2004 | 6/3/2004 | 6/3/2004 | P | PART |
Rick Jackson
|
|
|
Contact: Charles - Cover Inspection; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Need to complete the anti-freeze loop when the terrace is ready 6/3/2004 4:18:52 PM
|
INSP-Sprinkler Rough-in/Hydro | 5/27/2004 | 6/1/2004 | 6/1/2004 | A | FAIL |
Rick Jackson
|
|
|
Contact: Charles; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Heads overspaced in kitchen; tape on heads; need cages on heads in several areas; head in freezer appears to be leaking; need resubmittals for thatch canopies that have heads under them and for changes to under stair piping 6/1/2004 11:30:17 AM
|