Permit Number | FIR04-00230 |
Status | Finaled |
Name |
SIMPLEX/GRINNELL
|
Site Address |
107 N CASTELLO PL
|
Project Name | SPR BRUNO BUILT-MARSOLEK RES |
Customer Number | |
ePlanReview | |
Description |
To install a life safety fire sprinkler system in a new 4,275-ft/2 ft/2 two story single family dwelling with a 1,216-ft/2 unfinished basement, a 970 ft/2 attached three car garage. This lot is within a hillside area and is subject to the hillside ordinances. This structure shall be fitted with a 13D modified sprinkler system, which includes all closets, bathrooms and attached garage per Plat Notes. The sprinkler flow alarm shall be connected to the residence smoke detection system. Separate permitting will be required to finish the basement. All fire sprinkler work and related, which includes the dual use, single service water supply, the system backflow prevention device (provided by others), shall be per NFPA 13D, approved plans, engineering/red-lining and attached review comments/conditions, under direction of the Fire Chief. This permit is attached to: BLD03-02023.
|