Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR04-00245
StatusFinaled
Name HONEYWELL INC
Site Address 190 E BANNOCK ST
Project Namealm - ST LUKES
Customer Number 
ePlanReview 
Description
To provide required automatic detection and notification to an existing required manual fire alarm system that includes sprinkler monitoring, HVAC shutdown, elevator recall/shutdown and notification throughout.

The associated building permit (BLD 03-02465) is to build out and occupy approximately 26,900 sq.ft. of area on the ground floor, with associated work on the 1st & sub-basement levels, to be used for surgery suite and support areas per approved plans. To perform selective demolition to include structural modifications; to temporarily relocate certain essential hospital services, to continue in operation; to construct new interior non-bearing, non-combustible, fire-resistive walls to create groups of suites for operating rooms and support facilities throughout the ground floor. This project will involve Phases 1 & 2 as indicated on sheet G0.1 with six future phases requiring separate submittals and permits; to install two supply service elevator lifts & equipment rooms from the sub-basement to the ground floor; maintain existing fire-resistive ratings of 2-hour floors and shaft assemblies, create 1-hour occupancy fire barrier walls at incidental use areas and to create non-sleeping hospital suites; upgrade electrical, plumbing, mechanical, sprinklered and alarm systems to meet tenant needs and comply with current adopted codes and ordinances. PC03-630/drs (ST LUKES-EAST TOWER-1ST/GROUND/SB FLRS)(ETA SURGERY SUITE)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection10/22/200410/22/200410/22/2004APASS
DetailsRick Jackson
Hi Rick, Try ###-#### pager # 3006 Thanks, Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble
INSP-Final Inspection10/22/200410/22/200410/22/2004APASS
DetailsRick Jackson
INSP-Final Inspection10/20/200410/20/200410/20/2004PPART
DetailsRick Jackson
Hi Rick, We have the doors working and F/S all been gone thru. thanks Phil; Phone #: ###-#### Internet Inspection Request from: Phil Doble Need to verify door closures to OR's with fire alarm; all other items corrected - need NFPA 72 record of completion 10/20/2004 4:03:19 PM
INSP-Final Inspection10/11/200410/12/200410/12/2004AFAIL
DetailsRick Jackson
OR 11 has detectors overspaced; dampers at south area of 2 hour wall need to be on zone 5; detector 25 too close to diffuser; circuit 4 voltage drop too much 10/12/2004 12:33:26 PM
INSP-Final Inspection10/7/200410/7/200410/7/2004PPART
DetailsRick Jackson
Tested the area of east annex - okay; will need to test area west of 2 hour wall 10/8/2004 7:59:46 AM
FIR-Aging Inspection9/22/20049/22/20049/22/2004 PASS
DetailsRick Jackson
This project is still under construction 9/22/2004 9:49:12 AM