Information based on query as of Sunday, June 30, 2024.
Permit Information
Permit NumberFIR04-00267
StatusFinaled
Name PEAK ALARM
Site Address 4614 W STATE ST
Project Namealm -COLLISTER SHOPPING CNTR
Customer Number 
ePlanReview 
Description
To replace a sprinkler monitoring system with a code compliant system that includes HVAC shutdown and cooking hood monitoring.

The associated building permit (BLD 04-00222) is to remodel a 11,656 sq.ft. space for new retail tenant per approved plans. Work includes filling of sunken floor area with compacted fill and pouring a new concrete floor at grade with existing main level floor; construction of interior non-bearing walls to create the sales, stock room, office, two accessible restrooms & hallway areas; to construct two new exit doors in the exterior masonry walls; modify electrical, plumbing, mechanical, fire sprinkler and alarm systems; and new wall and floor finishes. This building is fully sprinklered for allowable area increase. PC04-074/drs (DOLLAR TREE STORE)(COLLISTER SHOPPING CENTER)
Contact Information
See Activities list for contact information
Show All Activities
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
INSP-Final Inspection5/26/20045/28/20045/28/2004PPASS
DetailsRick Jackson
###-#### peak or ###-####
INSP-Final Inspection5/13/20045/14/20045/14/2004APART
DetailsTroy Cobbley
A temporary occupancy was given with dave millers permission as long as a 24-hr/7-day/wk fire watch is in place until the fire alarm system has been finaled. Per Chris with Dollar Tree, United Security (###-####) has been hired. Items to be corrected include: Sample tubes on the duct smoke detectors are too short. Provide correct lenght tubes. Provide tamper switches on all anti-freeze loop control valves. Resubmit plans showing the additional control valve in the Dollar Tree space. Provide building map with correct device addresses. Provide cover on the electrical connections for the FACP. Provide connection to the hood suppression system and test. PIV supervisory signal lactched. Change to non-latching. Provide minimum 8.4 AH battery for the 12-volt side of the FACP. Test flow switch. Monitoring company does not have account set up for new alarm system/device addresses. Get account set up and retest all devices prior to calling for final inspection. 5/14/2004 1:47:12 PM